HL = 49 (120F)
The highest heating value permitted to be set by the user.
Adjustable between 0~35c (32~95F).
CL = 5 (41F)
The lowest cooling value permitted to be set by the user.
Adjustable between 5 ~37c. (41~98F).
CF = C
Temperature display Format
Deg C or deg F display type. (effects all user and installer menu items)
C1 = 0.0 Fitted Sensor Calibration
Calibration offset for the internal sensor.
Adjustable range +/‐ 4.5 deg C (+/‐9 F). in 0.1 steps
tC = 12
Time Clock
tC = 12 ‐ 12 Hour Time Clock.
tC = 24 ‐ 24 Hour Time Clock.
tC = 0 ‐ No time clock shown (Manual mode only –SW6=off)
td = 0
Temperature Display
TD = 00 ‐ The SMT‐770 will display both the room & set temperature.
TD = 01 ‐ The SMT‐770 will display set temperature only.
AH = 2
After Hours Override Timer
Start / Stop Mode ‐ Commercial Thermostat Mode (Sw6=on, Sw8=off)
After hour run time period ‐ Adjustable range 0 (off) to 12 hours in 0.5 hour steps.
Setback (1, 2, 3, 4) mode – Residential programmable mode (Sw6=on, Sw8=on)
Temporarily program override period.
Off= Override till next program change or 1‐12 hours (fixed time override)
22 | P a g e
Heating Limit (or High Limit)
Cooling Limit (or Low Limit)