Switch 1 – Relay Assignment 
The SMT‐770 is fitted with 5 relays capable of switching up to 24VAC @ 1Amp. Switch 1 
sets the function of these relays as either 3 fan speeds with 1 heat and 1 cool operation 
or single fan speed with 2 heat and 2 cool, in either HP (heat pump / reverse cycle) or 
HC (heat with add on cool) mode. 
 
Switch 2 – Equipment Type. 
Both  heat  with  add  on  cool  or  heat  pump  types  of  systems  can  be  controlled  by  the 
SMT‐770.  
Heat Cool System uses the "W" terminal(s) only for heating and the "Y" terminal(s) only 
for cooling. 
Heat  Pump  systems  use  the  "Y"  terminal(s)  for  BOTH  heating  and  cooling  (the 
compressor).  The  "W1"  terminal  to  control  the  reversing  valve  which  determines 
heating or cooling mode. 
 
Switch 3 – Equipment Stages. 
When it is necessary to control a single stage A/C system fitted with auxiliary heating 
elements,  turn  Sw3  OFF  thereby  selecting  single  stage  mode.  Heating  elements 
controlled by the W2 output are now assigned as stage 2 heat. 
 
Switch 4 – Reversing Valve or Fan Mode 
When  the  SMT‐770  is  set  for  Heat  Pump  mode  (Sw2  is  on)  then  this  switch  sets  the 
reversing  valve  logic  (O/B).  When  the  SMT‐770  is  set  for  Heat  Cool  mode  (Sw2  is  off) 
then this switch sets the mode for the Heater fan logic (HG or HE mode).