Start Program Temperature (Commercial Mode); Sc = Off Stop Cooling Temperature (Commercial Mode); Sh = Off Stop Heating Temperature (Commercial Mode); Db = 0.5/1 Single Set Point Dead Band - Smart temp SMT?770 Installer Manual

Chameleon multifunction thermostat
Hide thumbs Also See for SMT?770:
Table of Contents

Advertisement

St = Off 
Start Program temperature (Commercial Mode)
Start/stop mode Only. (Sw6=on, Sw8=off). 
This sets the default temperature that will be used each time the "Start" program 
begins regardless of any adjustments the user may have made previously. 
Adjustable between OFF, 15~35c. (59~95F). If set to off, the user set point will not 
be automatically reset to a default value each day. 
SC = OFf    Stop Cooling temperature (Commercial Mode)
Start/stop mode Only. (Sw6=on, Sw8=off). 
Cooling temperature that will be maintained when running the "STOP" program. 
(Night Setback) 
Adjustable between 5 ~37c. (41~98F) + OFF. 
SH = OFf   Stop Heating temperature (Commercial Mode)
Start/stop mode Only. (Sw6=on, Sw8=off). 
Heating temperature that will be maintained when running the "STOP" program. 
(Night Setback) 
Adjustable between 5 ~35c. (41~95F) + OFF. 
db = 0.5/1  Single Set Point Dead band (See page 33 for more information)
Dead band between heat and cool set point when in single set point mode  
(sw8 off). 
Adjustable between 0 and 5 deg in 0.5 c steps 
 
 
23 | P a g e
 
 