St = Off
Start Program temperature (Commercial Mode)
Start/stop mode Only. (Sw6=on, Sw8=off).
This sets the default temperature that will be used each time the "Start" program
begins regardless of any adjustments the user may have made previously.
Adjustable between OFF, 15~35c. (59~95F). If set to off, the user set point will not
be automatically reset to a default value each day.
SC = OFf Stop Cooling temperature (Commercial Mode)
Start/stop mode Only. (Sw6=on, Sw8=off).
Cooling temperature that will be maintained when running the "STOP" program.
(Night Setback)
Adjustable between 5 ~37c. (41~98F) + OFF.
SH = OFf Stop Heating temperature (Commercial Mode)
Start/stop mode Only. (Sw6=on, Sw8=off).
Heating temperature that will be maintained when running the "STOP" program.
(Night Setback)
Adjustable between 5 ~35c. (41~95F) + OFF.
db = 0.5/1 Single Set Point Dead band (See page 33 for more information)
Dead band between heat and cool set point when in single set point mode
(sw8 off).
Adjustable between 0 and 5 deg in 0.5 c steps
23 | P a g e