Fo = 0/2   Fan Options ‐ Advanced Fan Functions
This function is only enabled when the selected fan mode is Fan On.  
"FAN ON" will be displayed in the LCD to confirm this mode. 
 
FO = 0 ‐ (Default Residential mode).The fan will run continuously ‐, 24 hours a day 
7 days a week. 
 
FO  =  1  ‐  The  fan  will  continue  to  run  after  the  cooling  stops  to  ensure  the 
maximum  fresh  air  ventilation  and  to  aid  in  cooling.  The  fan  will  stop  after  the 
heating  stops.  (This  is  done  to  prevent  cold  drafts  that  may  occur  on  cold  days 
when A/C system is heating). 
 
FO  =  2  ‐  (Default  in  Start  Stop  Mode).Available  only  if  in  Programmable  Mode 
(Sw6=on). The Fan will Run continuously from program # 1 (or Start) Program to 
program #4 (or Stop) program and then run in AUTO mode overnight to maintain 
the night time set points.  
 
FO  =  3  ‐  Available  only  if  in  Programmable  Mode  (Sw6=on).  This  mode  is  the 
combination of option 1 and option 2 given above. 
FP = 0
Fan Purge Time Period (Fan run on)
If fan mode is Auto Fan, the indoor fan will run for FP=XX minutes after heating or 
cooling has stopped to extract any stored energy in the coils etc –  
(Necessary for electric element heating). 
Adjustable between off to 5 minutes in 1 minute intervals. 