Smart temp SMT?770 Installer Manual

Smart temp SMT?770 Installer Manual

Chameleon multifunction thermostat
Hide thumbs Also See for SMT?770:

Advertisement

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Installer Manual 
SMT‐770 Chameleon Multifunction Thermostat 
 
Ver 1.0 
 
 

Advertisement

Table of Contents
loading

Summary of Contents for Smart temp SMT?770

  • Page 1       Installer Manual  SMT‐770 Chameleon Multifunction Thermostat                                  Ver 1.0   ...
  • Page 2     This document it not typically left with the user as it contains information on setting  values which, if not correctly set may damage the heating, cooling or air conditioning  system or seriously affect its performance or energy consumption.        Great  effort  has  been  taken  to  making  the  SMT‐770  thermostat  system  intuitive,  reliable  and  easy  to  install.  Using  a  common  sense  approach  to  the  installation  will  ensure  this  product  is  installed  easily  and  to  the  customer’s  satisfaction.  Please  read  and understand this instruction manual so that installation, testing and commissioning ...
  • Page 3: Table Of Contents

    Table of Contents      Installation ........................  4   Mounting the wall controller ....................  5   Setting the hardware switches ...................  6   TT Terminal Functions ....................  9   Outside Air Sensor wiring ....................  1 0   Remote Air Temperature sensor wiring.  ................  1 0   Averaging Temperature sensors ..................  1 1   Remote ON / OFF function ....................  1 1   Using the “Occupancy Mode”  ...................  1 1   Typical Drawings  ......................  1 2  ...
  • Page 4: Installation

    Installation    As  with  any  air  conditioning  project  undertaken,  careful  installation  is  the  key  to  a  successful  outcome.  Time  taken  during  this  installation  process  will  be  rewarded  by  a  happy customer and fewer call‐backs.    The steps required to install the SMT‐770 thermostat are    Read and understand this manual and the User manual.  Mount the SMT‐770 back plate in a suitable location.  Set the 8 DIP switches to match the need of the project / user.  Wire the optional remote temperature sensor(s) or switches if required.  Power up the air conditioning system.  Set the installer software options (if required).  Program and set up the SMT‐770 thermostat.   (The User Manual will assist with this). ...
  • Page 5: Mounting The Wall Controller

    Mounting the wall controller   The  SMT‐770  can  only  be  as  accurate  as  the  onboard  temperature  sensor,  or  its  optional  remote  temperature  sensor(s)  permit.  It  is  therefore  essential  that  the  wall  thermostat be installed in a location that is typical of the ambient room temperature.  Do not install the thermostat in a draft, near a floor, behind doors or on a non‐insulated  external  wall.  Also  avoid  placing  the  thermostat  in  areas  where  the  air  movement  is  limited, ...
  • Page 6: Setting The Hardware Switches

    Setting the hardware switches    Switch  On  Sw1 – Fan Speeds  1 Speed Fan 3 Speed Fan (2 heat / 2 Cool)  (1 heat / 1 Cool)  Sw2 – Equipment Type  Heat Cool Heat Pump (O/B terminals) Sw3 – Stages  1 Stage  2 Stages Sw4 – Reversing Valve  Energise in cool (O) Energise in heat (B)         If Sw 2= ON – Heat Pump Sw4 – Fan Mode  Fan Control by Heater (HG) Fan Control by T’stat (HE)         If Sw 2= OFF – Heat/cool Sw5 – Anti cycle timer  4 Minutes Sw6 – Operation  Manual Thermostat Programmable Thermostat Sw7 – Minimum Run  2 minutes 6 Minutes Sw8 – Program Type Commercial Program Residential Program          If Sw 6= ON – Programmable Sw8 – Set points Single Set point Two Set points...
  • Page 7 Switch 1 – Relay Assignment  The SMT‐770 is fitted with 5 relays capable of switching up to 24VAC @ 1Amp. Switch 1  sets the function as either 3 fan speeds with 1 heat and 1 cool operation or single fan  speed  with  2  heat  and  2  cool,  in  either  HP  (Heat  pump  or  reverse  cycle)  or  HC  (heat  with add on cool) mode.    Switch 2 – Equipment Type.  Both  heat  with  add  on  cool  or  heat  pump  types  of  systems  can  be  controlled  by  the  SMT‐770.  ...
  • Page 8 Switch 5 – Anti Cycle Timer  To  protect  some  A/C  systems  it  is  preferred  that  under  no  circumstances  should  the  compressor start within 4 minutes of it switching off.   Note, when power is first applied to the SMT‐770 it “assumes” that the compressor has  just stopped and applies this anti cycle delay time before starting.    Switch 6 – Thermostat Operation  To  suit  the  varying  requirements  of  the  user,  the  SMT‐770  can  be  set  as  a  programmable  thermostat  using  the  time  clock  to  automatically  control  the  building  temperature ...
  • Page 9: Tt Terminal Functions

    Switch 8 – Thermostat Control Logic.  This  switch  also  has  two  functions  based  on  the  position  of  switch  6.  When  the   SMT‐770  is  set  as  a  programmable  thermostat  switch  8  determines  whether  a  commercial  program  or  residential  program  is  selected.  When  switch  6  has  the   SMT‐770 ...
  • Page 10: Outside Air Sensor Wiring

    Outside Air Sensor wiring    Set “TT= OA” in the advanced installer menu.  RS-01 SMT-770 The SMT‐770 can display the outside air temperature if  desired. Some advanced control functions such as high  and low balance points rely on this sensor to be fitted  Figure 1  for  correct  operation.  Using  a  single  pair  of  wires  connect  the  “TT”  terminals  in  the  SMT‐770  to  the  two  terminals  in  the  outside  air  temperature  sensor.  (See  figure  1).  If  the  outside  air  sensor  fails  two  dashes  will  be  shown on the LCD where the outside air temperature would normally be displayed to ...
  • Page 11: Averaging Temperature Sensors

    Averaging Temperature sensors  Set “TT= AV” in the advanced installer menu.  The  SMT‐770  can  average  the  sensed  temperature  equally  between  the  remote  temperature  sensor(s)  and  the  one  fitted  to  the  SMT‐770  if  required.  See  figure  1  on  the  previous  page  for  details  on  wiring  the  sensor.  The  SMT‐770  will  auto‐detect  this  sensor ...
  • Page 12: Typical Drawings

    Typical Drawings    The  SMT‐770  has  the  capacity  to  control  a  wide  selection  of  heating,  cooling  and  air  conditioning systems. Using the DIP switches and installer software options, the SMT‐ 770  is  capable  of  providing  more  than  96  different  control  methods  from  its  5  fitted  relays. Examples of only the most common types of control wiring have been provided  below.    You  may  need  to  modify  these  drawings  to  specifically  suit  your  individual  needs ...
  • Page 13     Switch Settings  Sw1 = Off (1 speed fan)  Sw2 =Off (HC System)  Sw3=Off (Single Stage)  Sw4= OFF (HG)  Sw5= Installer preference  Sw6= User requirements  Sw7= Installer preference  Sw8= User requirements          Figure 5     Switch Settings  Sw1 = Off (1 speed fan)  Sw2 =Off (HC System)  Sw3=On (Two Stage)  Sw4= OFF (HG)  Sw5= Installer preference  Sw6= User requirements  Sw7= Installer preference  Sw8= User requirements      Figure 6   13 | P a g e    ...
  • Page 14       Switch Settings  Sw1 = On (3 speed fan)  Sw2 =On (HP System)  Sw3=Off (One Stage)  Sw4= Equipment Specific         On = B   Off = O  Sw5= Installer preference  Sw6= User requirements  Sw7= Installer preference  Sw8= User requirements    Figure 7     Switch Settings  Sw1 = Off (1 speed fan)  Sw2 =On (HP System)  Sw3=On (Two Stage)  Sw4= Equipment Specific         On = B   Off = O  Sw5= Installer preference  Sw6= User requirements  Sw7= Installer preference  Sw8= User requirements     Note: Set W3=EH   Figure 8 in installer menu.  14 | P a g e    ...
  • Page 15     Switch Settings  Sw1 = Off (1 speed fan)  Sw2 =On (HP System)  Sw3=Off (One Stage)  Sw4= Equipment Specific         On = B   Off = O  Sw5= Installer preference  Sw6= User requirements  Sw7= Installer preference  Sw8= User requirements   Note: Set W3=OF in  installer menu.    Figure 9     Switch Settings  Sw1 = On (3 speed fan)  Sw2 =On (HP System)  Sw3=Off (One Stage)  Sw4= Equipment Specific         On = B   Off = O  Sw5= Installer preference  Sw6= User requirements  Sw7= Installer preference  Sw8= User requirements                                                                         Figure 10  15 | P a g e    ...
  • Page 16: Attaching The Thermostat

    Attaching the thermostat    Check  that  the  position  of  the  8  DIP  switches  matches  the  requirements  of  the  equipment  being  controlled  and  the  specific  requirements  of  the  user.  Detailed  information on the 8 DIP switches can be found on page 6 of this manual.    Check the wiring matches that of the equipment the SMT‐770 is to control and that all  wiring  is  tight  and  not  likely  to  short  between  adjacent  wires.  Equipment  wiring  information can be found on page 12 of this manual. ...
  • Page 17: Advanced Installer Settings

    Remove and discard the plastic tab on the internally fitted backup battery so that the  battery is now in circuit and operating.    Avoid twisting the case as this may stress the LCD and cause it to crack. Avoid running  wiring near the internally fitted sensor.    Take care not to damage or crush the temperature sensor between the two half’s of  the case when you close the Chameleon case. Check this sensor location.  Advanced Installer Settings    The  SMT‐770  is  fitted  with  many  advanced  functions  that  can  be  fine  tuned  by  the  installer to specifically match the needs of the project of the user.     Normally these functions will not need to be altered from the factory default position  however, there may be times when you wish to alter a setting or control capability so  that  the  SMT‐770s  performance  will  perfectly  match  a  particular  application.  On  the  next ...
  • Page 18  Using the Installer Menu    To move forward through the Installer menu items tap the “O/RIDE” button.    To move backwards through the Installer menu items tap the “PROG” button.    To adjust a value in the Installer menu tap the ( ) or down ( ) buttons.    To exit the installer menu tap the “Mode” button, the “Fan” button or wait 60 seconds.     Entering the Installer Menu    To enter the Installer menu, press and hold the O/RIDE button for 15 seconds. After 15  88:15” seconds the LCD will show “  – The factory default PIN.    88:21” Adjust this value to “  (or your previously selected value) by using the up ( ) or  down ( ) button. Tap the O/RIDE button to enter the menu.     If you have entered the correct PIN you will be given the first menu option, if you have  entered a incorrect PIN you will be exited from this menu.     Default Installer Values are shown in the examples below. 18 | P a g e    ...
  • Page 19   PN =21  Keyboard Lock PIN This is the required PIN for future entry into the Installer menu.  Range 00 to 99 in 01 steps.   (Caution,  if  you  change  this  value  and  forget  your  new  PIN,  you  may  need  to  return the SMT‐770 to place of purchase for unlocking  ‐ there may be a fee for  this service)  LC=0   Keyboard Lock level Programmable Mode (SW6=ON)  LC=00 ‐ Key board Lock OFF.  LC=01 ‐ All buttons are locked.   LC=02 ‐ All buttons are locked except the O/Ride button.  LC=03 ‐ All buttons are locked except the Mode and O/Ride buttons.  LC=04 ‐ All buttons are locked except the Mode button.    Manual Mode (SW6=Off)  LC=00 ‐ Key board Lock OFF.  LC=01 ‐ All buttons are locked except the Mode button.  LC=02 ‐ All buttons are locked except the Mode and temperature +/‐ button.  LC=03 ‐ Fan & O/ride buttons are locked.                 Mode button can only select Auto (Heat & Cool) and off.  LC=04 ‐ O/Ride Button is locked                  Mode button can only select Auto (Heat & Cool) and off.  (Note ( ) or down ( ) buttons can be limited in the HL & CL menu items)  19 | P a g e  ...
  • Page 20 HL=35 (95F)  Heating Limit (or High Limit) The highest Heating value permitted to be set by the user.    Adjustable between 0~35c (32~95F).  CL =5 (41F) Cooling Limit (or Low Limit) The lowest Cooling value permitted to be set by the user.    Adjustable between 5 ~37c. (41~98F).  CF=C    Temperature display Format Deg C or deg F display type. (effects all user and installer menu items)  C1 =0.0     Fitted Sensor Calibration  Calibration Offset for the internal sensor.  Adjustable range +/‐ 5 deg C (+/‐9 F).  tC =12   Time Clock   Display 12 or 24 hour Clock Style.  tD =0   Temperature Display  TD=00 ‐ The SMT‐770 will display both the Room & Set Temperature.  TD=01 ‐ The SMT‐770 will display set temperature only.  AH=2   After Hours Override Timer  Start / Stop Mode  ‐ Commercial Thermostat Mode (Sw6=on, Sw8=off)  After hour run time period ‐ Adjustable range 0 (off) to 12 hours.  Setback  (1,  2,  3  ,4)  mode  –  Residential  programmable  Mode  (Sw6=on,  Sw8=on)  Temporarily program override period.   Off= Override till next program change or 1‐12 hours (fixed time override)  20 | P a g e  ...
  • Page 21 SC=OFf    Stop Cooling temperature Start/stop mode Only. (Sw6=on, Sw8=off).  Cooling temperature that will be maintained when running the “STOP” program.  (Night Setback)  Adjustable between 5 ~37c. (41~98F) + OFF.  SH= OFf   Stop Heating temperature Start/stop mode Only. (Sw6=on, Sw8=off).  Heating temperature that will be maintained when running the “STOP” program.  (Night Setback)  Adjustable between 5 ~37c. (41~98F) + OFF.  Db=1   Single Set Point Dead band (See page 27 for more information) Dead band between heat and cool set point when in single set point mode (sw8  off).  Adjustable between 0 and 5 deg      21 | P a g e    ...
  • Page 22 FO=0/2   Fan Options ‐ Advanced Fan Functions This function is only enabled when the selected fan mode is Fan On.   “FAN ON” will be displayed in the LCD to confirm the mode.    FO=0 ‐ (Default).The fan will run continuously ‐, 24 hours a day 7 days a week.    FO=1 ‐ The fan will continue to run after the cooling stops to ensure the maximum  fresh air ventilation and to aid in cooling. The fan will stop after the heating stops.  (This is done to prevent cold drafts that may occur on cold days when A/C system  is heating).    FO=2(Default  in  Start  Stop  Mode).Available  only  if  in  Programmable  Mode  (Sw6=on). The Fan will Run continuously from program # 1 (or Start) Program to  program #4 (or Stop) program and then run in AUTO mode overnight to maintain  the night time set points.     FO=3  ‐  Available  only  if  in  Programmable  Mode  (Sw6=on).  This  mode  is  the  combination of option 1 and option 2 given above.  FP=1 ...
  • Page 23 Fn=A   Function ‐ Available Equipment Modes  FN=A ‐ Select if controlling a Heating & Cooling system.  FN=C ‐ Select if controlling a Cooling only system. (disables heating menus)  FN=H ‐ Select if controlling a Heating only system. (disables cooling menus)  H3=Of  W2 relay Function Only operates in single fan speed HP mode.  (Sw 1=off & Sw2=on).  H3=Of ‐ W2 relay is used as 2nd (or 3rd) stage Auxiliary heat.  H3=EH ‐ W2 relay is used to control an Emergency Heating system.  H3=AH ‐ W2 relay is used to control a Add On Heat system.  tt=RS  TT terminal Function  (see page 9 for more detail on this function) TT=OA ‐ Connect the outside air temperature sensor to the TT terminals to display  the outside Air Temperature.    (Required for all outside air control functions to operate.)  TT=RS  ‐  Connect  the  remote  room  temperature  sensor  to  the  TT  terminals  to  measure the temperature at a remote location away from the SMT‐770.  (Note: This completely disables the temperature sensor fitted to the SMT‐770)  TT=AV ‐ The TT terminals will average the temperature measured by the SMT‐770  internal sensor and remote room temperature sensor.  TT=OF – A closed contact on the TT terminals will switch the SMT‐770 On or OFF.  (More detail on this function provided on page 11 of this manual.)  TT=OC ‐ A closed contact on the TT terminals will switch the SMT‐770 to Occupied  Mode, where the oC & oH temperatures will replace the user set temperatures.  (See page 11 of this manual for more detail on this function.) ...
  • Page 24 AF=0  Anti‐Freeze Function AF=0 ‐ Antifreeze function off.  AF=1 ‐ Room temperature will not be permitted to fall below 5c (41F).  oH=Off  Occupied Mode Heat Set  (see page 11 for more information). Only operates if TT=OC.  This  is  the  heating  temperature  that  will  be  used  in  “Occupied  mode”  and  will  temporarily  replace  the  user  heat  set  point  while  the  TT  terminals  are  shorted  together.  oC=OFf   Occupied Mode Cool Set  (see page 11 for more information). Only operates if TT=OC. ...
  • Page 25 Sd=2   Stage 2 Span (See page 27 for an overview of this control function) Hysteresis for Stage 2.   (difference between heating and cooling turning on and off)  Sd=1  0.5c  Sd=2  1.0c  Sd=3  1.5c  DT=35   Upstage delay time Time in minutes before next stage of heating or cooling is to be called.   Delay only operates if stage trip temperature has not yet been reached.  Adjustable between 10 ~ 90 Minutes in 5 minute steps.  OS=0   Optimised Start/stop. (Adaptive Recovery)  OS=0 ‐ Optimised start/stop function Off.  OS=1 ‐ Optimised start/stop function running.  (See page 35 for more information on this function)  C2=0.0   Calibration Remote Sensor Calibration Offset for the TT terminal temperature sensor.   Adjustable range +/‐ 5 deg C (+/‐9 F).  Co=0(41F)  Cooling OFF temperature.  ‐ See page 34 for more detail. Only operates if TT=OA and outside temperature sensor is fitted.  Outside air temperature below this value will force the cooling function OFF.  Adjustable between 5 ~37c. (41~98F).      25 | P a g e    ...
  • Page 26 Ho=35 (95F) Heating OFF temperature. ‐ See page 34 for more detail. Only operates if TT=OA and outside temperature sensor is fitted.  Outside air temperature above this value will force the heating function OFF.  Adjustable between 5 ~37c. (41~98F).  HB=37 (98F) High Balance Point.  ‐ See page 33 for more information. TT=OA, the outside temperature sensor must be fitted and Sw 1=off.  2nd  (or  3rd)  stage  heating  is  locked  out  when  the  outside  air  is  above  this  temperature.  Adjustable between 5 ~37c. (41~98F).  LB=9.5 (15f) Low Balance point. ‐ See page 33 for more information. TT=OA, the outside temperature sensor fitted, H3=EH, Sw 1=off and Sw2=on.  Outside temperatures below this value will automatically select Emergency Heat  mode.  Adjustable between ‐9.5 ~37c. (15~98F).  Ft=off   Filter warning time Return air filter cleaning warning time.  Adjustable between off and 900 hours.  Ad=07   Modbus Address. See page 32 for more information. Modbus communications address ...
  • Page 27 tS=0   Factory test mode ‐ See page 33 for more information. TS=0 ‐ Factory test Mode OFF.  TS=1 ‐ Display configuration code.*  TS=2 ‐ Step cycle all relays in sequence, 1 2 3 4 5 etc.  (* this code table is available from the download section at www.thermostat.com.au)    Control logic    Single Set Point mode Two Set Point mode This  simple  diagram  provides  a  general  insight  into  the  control  logic  of  the  SMT‐770  thermostat.  It  attempts  to  describe  the  action  of  the  DB=XX,  the  SP=XX ...
  • Page 28: Commissioning

    Commissioning    As with any thermostat, commissioning ensures that the thermostat and the equipment  connected  to  it  are  operating  correctly  and  as  expected.  Although  the  SMT‐770  is  a  multifunctional thermostat, commissioning is quite a  simple process. Follow the steps  detailed  below  and  use  the  trouble  shooting  guide  on  page  37  if  you  encounter  a  problem.     When the thermostat is fitted to the base plate and when 24VAC power is first applied,  the  LCD  should  briefly  show  all  available  segments  (a  LCD  function  test),  then  display  the time and operating mode etc. ...
  • Page 29   If  you  choose  not  to  use  commissioning  mode  you  may  see  various  words  and  Icons  flashing  in  the  LCD  when  ever  a  time  period  is  in  use.  For  example,  the  word  “HEAT”  may flash to indicate heating is required but being held off by the 4 minute anti‐cycle  timer. Or the word “HEATING” may be flashing to indicate set point has been achieved  however heating is being held ON by the minimum run timer.    The golden rule with the SMT‐770 is anything that flashes is a time period overriding  what would normally be expected to occur; either a function is being held on or off  momentarily.  Please be patient.   ...
  • Page 30 “Heat”  will  change  to  “Heating”.  Verify  that  the  heating  system  is  on  and  operating  correctly.    Using the temp + or Temp – button set the desired temperature a few degrees above  the  ambient  temperature.  After  a  few  moments  you  will  hear  a  click  and  the  word  “Cool”  will  change  to  “Cooling”.  Verify  that  the  cooling  system  is  on  and  operating  correctly.  ...
  • Page 31: Using Remote Temperature Sensors

    Using Remote Temperature Sensors    Figure 12        Single Sensor  Twin Averaging Sensors  Three Averaging Sensors  Single or multiple room air temperature sensors can be connected to the SMT‐770   “TT” terminals if temperature averaging over a larger area is desired. Shown are   4  examples  of  commonly  used  sensor  configurations.  Note  ‐  Either  TT=RS  (remote  sensor) or TT=Av (Averaging sensors) value must be set in the advanced installer menu  for these sensors to be used.    Please note the configuration of RS‐01 &  RS‐02 sensors in the examples provided  above.  Other  sensor  configurations  are  also available.        Four Averaging Sensors  31 | P a g e  ...
  • Page 32: Advanced Functions

    When  used  in  Start  /  Stop  commercial  programmable  mode  (SW6=on  SW8=off),  the  after  hours  run  timer  can  be  toggled  on  or  off  as  required  with  a  momentary  press  button on the remote sensor.  See figure 14 Left.    In line On/Off As  the  SMT‐770  “Auto  detects”  sensors  connected  to  the  In line Switch Override...
  • Page 33   The  communications  port  of  the  SMT‐770  has  3  terminals  marked  “A”,  “B”  &  “C”.  Terminals  “A”  &  “B”  are  used  for  communication,  terminal  “C”  is  used  as  a  screen  ground to  protect the integrity of the communication  To Network signal.    Figure 15 A maximum of 35 SMT‐770s can be connected to any  single  hub.  Each  SMT‐770  on  the  hub  must  have  a  unique  network  address  (factory  default is 7). These settings are adjustable from the advanced installer menu. See page ...
  • Page 34 High Balance point    Set the installer menu value “HB=XX”.   When the outside air temperature is above this value, second or third stages of heating  are held off regardless of the room and set temperature.  Set this function to prevent the excessive consumption of energy when the outside air  temperature is warm enough not to require additional heating stages to be used.    Low Balance point    SW2=on,  W3 =EH (Emergency Heat Mode) Set the installer menu value “LB=XX”.   When  the  outside  air  temperature  is  below  this  value  the  SMT‐770  will  automatically  switch  to  emergency  heat  mode  when  only  use  the  emergency  heating  system  when  heating is required. If the outside temperature is above this LB=XX value the emergency  heat mode can be selected manually at anytime with the “MODE” button.    Setting up the Heat & Cool Off functions  To  conserve  energy,  the  SMT‐770  can  suspend  the  heating  or  cooling  functions  if  the  outside air temperature is within a prescribed installer set range. ...
  • Page 35 Adaptive recovery  Only available in programmable mode (sw6=on).  The adaptive recovery function of the SMT‐770 permits the user to program a time that  a desired set temperature is required, letting the thermostat calculate the most energy  efficient time to turn on to achieve the desired temperature at the selected time.    For example, if the user typically returns home at 5:00pm at the end of the work day,  setting program #3 (if used in residential programmable mode) to 5:00pm the SMT‐770  will  calculate  the  most  energy  efficient  time  based  on  set,  room  temperature  and  history of temperature change to bring on the Equipment to meet the set temperature  by 5:00pm.    Adaptive recovery may also prevent the SMT‐770 from running for a few moments just  prior to a program change occurs.    “RECO” is shown in the LCD when ever Adaptive recovery is being used.      35 | P a g e    ...
  • Page 36: Specifications

    Specifications    Input Voltage   24VAC 50/60 Hz +/‐ 15%.  Relay rating  24VAC @ 1Amp maximum per relay.  Operating Temperature   0‐50C (32 to 122F).  Operating RH   0‐95% (non condensing).  Storage Temperature  0‐65C (32 to 150F).  Size   113 x 103 x 23mm.  Display Size   74 x 55mm.  Temperature Sensor(s)   10K NTC type 3.  Accuracy  +/‐ 0.3deg C @ 25 C. (77F)  Stage Delays  Minimum temperature change over time method.  Timed upstage Delay  5~90 minutes.  Anti‐cycle Delay  Off to 4 minutes.  Maximum hourly cycles  Unlimited, 30, 10 or 6. (Installer set)  Display resolution   0.5 deg C (1F).  Control Range   Off to 38c (100F).  Outside Air temp display range  ‐8 ~ +60c (17 ~ 140F).  Back light    Blue EL.  Backlight life  3,000 hours to half brightness.  Optimised Start/Stop method   Time to start vs temp differential method ‐ updating.  Communications Protocol ...
  • Page 37: Troubleshooting

    Troubleshooting    Symptom  Suspected Fault  Suggested remedy    Air from the wall cavity may be leaking into the  Plug holes in wall with tape to prevent leaks  Temperature display  rear of the thermostat / sensor enclosure.  seems inaccurate  The  internally  fitted  temperature  sensor  is  Carefully  move  the  room  temperature  folded back inside the Chameleon and not being  sensor  bead  so  that  it  is  just  behind  the  exposed to the room air temperature.  sensor opening in the case.  External  heat  or  cool  source  such  as  lamps,  Move ...
  • Page 38 Symptom  Suspected Fault  Suggested remedy  The word OFF is flashing in  This is not a fault  TT=Of in advanced installer menu.  the LCD. Mode button has  no effect.  Some buttons do not    LC=XX  value  in  advanced  installer  mode  set  appear to operate.  Key board lock is on.  the lock values, see page 17.  Padlock is show on LCD.    Cannot enter heat or cool  SMT‐770  thermostat  set  for  Heating  or  cooling  Heating  or  cooling  mode  not  available  on  modes  only modes  your air conditioning system  Cannot set heating and ...
  • Page 39: Specifications

    Specifications    Input Voltage   24VAC 50/60 Htz +/‐ 15%.  Relay rating  24VAC @ 1Amp maximum.  Operating Temperature   0‐50C (32 to 122F).  Operating RH   0‐95% (non condensing) .  Storage Temperature  0‐65C (32 to 150F).  Size   113 x 103 x 23mm.  Display Size   74 x 55mm.  Temperature Sensor(s)   10K NTC type 3.  Accuracy  +/‐ 0.3deg C @ 25 C. (77F)  Stage Delays  Minimum temperature change over time method.  Timed upstage Delay  5~60 minutes.  Anti‐cycle Delay  Off to 4 minutes.  Maximum hourly cycles  Unlimited, 30, 10 or 6. (Installer set)  Display resolution   0.5 deg C (1F).  Control Range   Off to 38c (100F).  Outside Air temp display range  ‐8 ~ +60c (17 ~ 140F).  Back light    Blue EL.  Optimised Start method   Time to start vs temp differential method.  Communications Protocol  Modbus – contact Smart Temp for objects list.  Fan speeds ...
  • Page 40                                         Smart Temp Head Office  Email  ‐ info@smarttemp.com.au  Unit 20 / 1488 Ferntree Gully Road  Web ‐ www.smarttemp.com.au  Knoxfield  3180 Victoria Australia. Phone +61 3 9763 0094  .    Fax + 61 3 9763 0098        This product has been manufactured by Smart Temp Australia.   Intellectual rights apply ‐ all rights reserved.  This product is Patent Pending.      40 | P a g e  ...