4.2

Specifications

4.2.1

General Specifications

Item
Rated operating voltage
Operating voltage range
Rated current consumption
Allowed momentary power off time
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
Breakdown voltage
Insulation resistance
Vibration resistance
Shock resistance
Noise immunity
Operating condition
Description
24V DC
21.6V to 26.4V DC
150mA or less
10ms at 21.6V, 10ms at 24V
0°C to +55°C/32°F to +131°F
−20°C to +70°C/−4°F to +158°F
30% to 85% RH (non-condensing)
30% to 85% RH (non-condensing)
500V AC for 1 minute between S−LINK terminal block and power supply/
ground terminals
min. 100MΩ (measured with a 500V DC megger)
between S−LINK terminal block and power supply/ground terminals
10Hz to 55Hz, 1 cycle/min: double amplitude of 0.75mm/ 0.030in., 10 min on
3 axes
2
Shock of 98m/s
or more, 4 times on 3 axes
1,000 Vp-p with pulse widths 50ns and 1µs (based on in-house measure-
ments)
Free from corrosive gases and excessive dust