Checking Status With Pmget Instruction; Specifications Of Pmget Instruction; List Of Communication Parameters - Panasonic FP7 Series User Manual

Hide thumbs Also See for FP7 Series:
Table of Contents

Advertisement

10.3 Checking Status with PMGET Instruction

10.3.1 Specifications of PMGET Instruction

Confirmation of error information
● Describe UNITSEL instruction immediately before PMGET instruction, and specify the slot
and port numbers of the unit to be read.
● Specify the type of data to be read (parameter or monitor information) for operand S1 of
PMGET instruction.
● Store 26 words for communication parameters or 7 words for monitor information in the area
starting with the area specified by operand S2 of PMGET instruction.

10.3.2 List of Communication Parameters

Acquisition of SCU communication parameters
Operand
Parameter
Communication
[D]
mode
[D+1]
Unit number setting
[D+2]
Baud rate setting
[D+3]
Data length setting
[D+4]
Parity setting
[D+5]
Stop bit length setting U0 to U1
WUME-FP7COM-07
10.3 Checking Status with PMGET Instruction
Range
Settings
U0
U0: MEWTOCOL-COM
U1
U1: MEWTOCOL7-COM
U2
U2: MODBUS RTU
U8
U8: General-purpose communication
U9
U9: PLC Link
Unit number U1 to U999
MEWTOCOL-COM: U1 to U99
U1 to U999
MEWTOCOL7-COM: U1 to U999
MODBUS-RTU: U1 to U247
PLC link: U1 to U16 (Default: 0)
U0: 300, U1: 600, U2: 1200, U3: 2400, U4: 4800, U5:
U0 to U10
9600, U6: 19200, U7: 38400, U8: 57600, U9: 115200,
U10: 230400 bps
U0 to U1
U0: 7-bit length, U1: 8-bit length
U0 to U2
U0: No parity, U1: Odd parity, U2: Even parity
U0: 1 bit, U1: 2 bits
10-7