7.3

Grounding

Under normal conditions, the inherent noise resistance is sufficient. However, in
situations of excess noise, ground the instrument to increase noise suppression.
For grounding purposes, use wiring with a minimum of 2 mm
connection should have a resistance of less than 100 Ω.
Other
FP0
device
CORRECT
Notes
The point of grounding should be as close to the FP0 control
unit as possible. The ground wire should be as short as
possible.
If two devices share a single ground point, it may produce an
adverse effect. Always use an exclusive ground for each
device.
Depending on the surroundings in which the equipment is
used, grounding may cause problems.
<Example>
Since the power supply line (24 VDC and GND terminal) of the
FP0 power supply connector is connected to the frame ground
(F.G.) through a varistor, if there is an irregular potential
between the power supply line (24 VDC and GND) and earth,
the varistor may be shorted.
24 V DC
FP0
Power supply connector
of FP0 control unit
GND
Varistor
F.G.
Other
device
Power supply lines
Varistor (39 V DC)
Wiring
7.3
Grounding
2
. The grounding
7 − 7