Description
Electrical Specifications:
AC Line Input:
Rated Voltage
Frequency Ranges
Rated Current
AC Output:
Output VAC
(On Line Power)
Rated Power
Loading(% of rated power in
Normal (not Bypass) mode):
0 - 110%
110 - 130%
> 130%
Voltage Normal
Mode
Current:
Maximum
Supported Load
Chrst Factor
Waveshape
Transfer Time
Phasing
Safety Agency Approvals
Fuse
B-24
A2998A PowerTrust UPS Specifications
Table B-25.
200 - 240 VAC 50/60 Hz (300 VAC Max)
47 - 53 Hz or 57 - 63 Hz
20.0 Amps (30 Amp max. branch circuit overcurrent protection)
Same as line input power
Up to 3000 VA
Up to 3000 Watts (Power factor of 1.0 assumed)
UPS will operate indefinitely
UPS will operate for up to 5 minutes
UPS will operate for <10 seconds
223 - 237 VAC
47 - 53 Hz or 57 - 63 Hz
13 Amps (rms)
<3 Amps peak/Amps rms)
True sine wave with < 5% total harmonic distortion
AC Failure - < 10 msec to switch to battery power
Input disconnect delay - 4 msec
AC Restored -20 Sec delay returning to phase lock with input AC
Phase locked to within 5º of input utility AC
UL, CSA, and TUV
20 Amp/250 VAC UL Listed Time Delay (Slow-Blow) Type
.