HP 3000 9X9/KS Site Preparation And Requirements Manual page 46

Enterprise servers
Hide thumbs Also See for 3000 9X9/KS:
Table of Contents

Advertisement

Description
Operating Altitude Range
Non-operating Altitude
Range
Heat Dissipation
Acoustics
Safety
B-4
Table B-9. Environmental Specifications. (Continued)
HP 9000 -
K100, K200, K210, K220,
K400, K410, & K420
HP 3000 -
929KS, 939KS, 959KS,
969KS/x00, & 969KS/x20
0 to 3048 m (0 to 10,000 ft.)
above sea level
0 to 4572 m (0 to 15,000 ft.)
above sea level
4263 BTU/hr
(Maximum Load)
Deskside (LwA) = <4.7 Bel at
Operator Post
Racked System (LwA) = <5.5 Bel at
UL Listed to UL1950
CSA Certified to CSA C22-2 No. 950
TUV GS Mark, compliant with
EN60950, and EN41003
Specification
HP 9000 -
HP 3000 -
0 to 3048 m (0 to 10,000 ft.)
above sea level
0 to 4572 m (0 to 15,000 ft.)
above sea level
5846 BTU/hr
Deskside (LwA) = <4.7 Bel at
< 31° C (<88° F)
<5.1 Bel at
<31° C (<88° F)
= 45 dB-LpA
Operator Post
no prominent tone
Racked System (LwA) = <5.5 Bel at
< 31° C (<88° F)
<5.1 Bel at
<31° C (<88° F)
UL Listed to UL1950
CSA Certified to CSA C22-2 No. 950
TUV GS Mark, compliant with
EN60950, and EN41003
K250, K260, K450, & K460
979KS
(Maximum Load)
< 31° C (<88° F)
<5.1 Bel at
<31° C (<88° F)
= 45 dB-LpA
no prominent tone
< 31° C (<88° F)
<5.1 Bel at
<31° C (<88° F)

Advertisement