Cabinet Specifications

Description
PDU Input Voltage
PDU Current (Max.) 16 Amps
PDU Electrical
Outlets Provided
ii
Electrical
Receptacle Required
Cooling Fans
i.
This cabinet model is only available in the EPS 22 configuration and does not include a fan or a PDU assembly.
ii.
PDU Input plug/receptacle types and numbers will vary depending on the PDU option(s) selected. An optional second PDU
can be installed. Optional higher current (20 Amp) PDUs are available for cabinets with Uninterruptible Power Supplies (UPS)
installed.
Description
Height
Width
Depth
Weight
Crated
Uncrated
Cooling and Access
Cabinet Electrical Specifications.
Table B-17.
A1896A (C2785A)
1.1 Meter Cabinet
100-120/200-240 VAC
(Nominal)
6/10 Depending on option
5-20P, L5-20P, L6-20R, L6-30P, IEC-320 (C19/20) NEMA depending on PDU
option selected. International Power cord supplied with no plug installed
2 (Optional)
Cabinet Physical Specifications
Table B-18.
A1896A (C2785A)
1.1 Meter Cabinet
112.01 cm (44.1 inches)
48.26 cm (19.0 inches)
71.60 cm (28.2 inches)
119.0 kg (262.4 lbs.)
81.0 kg (178.5 lbs.)
60.90 cm (24.0 inches)
(Front & Rear)
Specification
A1897A (C2786A)
1.6 Meter Cabinet
100-120/200-240 VAC
(Nominal)
16 Amps
6/10 Depending on option
2 (Optional)
Specification
A1897A (C2786A)
1.6 Meter Cabinet
162.00 cm (63.8 inches)
48.26 cm (19.0 inches)
71.60 cm (28.2 inches)
140.0 kg (308.6 lbs.)
100.0 kg (220.4 lbs.)
60.90 cm (24.0 inches)
(Front & Rear)
i
A3656A
(C2787A)
2.0 Meter Cabinet
100-120/200-240 VAC
(Nominal)
16 Amps
6/10 Depending on option
2 (Optional)
.
A3656A (C2787A)
2.0 Meter Cabinet
20.19 cm (79.5 inches)
48.26 cm (19.0 inches)
71.60 cm (28.2 inches)
175.0 kg (385.8 lbs.)
116.0 kg (255.7 lbs.)
60.90 cm (24.0 inches)
(Front & Rear)
B-11