Table B-24. A2997A Powertrust Ups Specifications - HP 3000 9X9/KS Site Preparation And Requirements Manual

Enterprise servers
Hide thumbs Also See for 3000 9X9/KS:
Table of Contents

Advertisement

Table B-24.
Description
Electrical Specifications:
AC Line Input:
Rated Voltage
Rated Current
AC Output:
Output VAC
(On Line Power)
Output VAC
(On Battery)
Rated Voltage &
Current
Supported Load
Crest Factor
Rated power VA
Rated Power Watts 1800 Watts assuming a 1.0 power factor
Waveshape
Transfer Time
Phasing
Safety Agency Approvals
Fuse
A2997A PowerTrust UPS Specifications
100/120-127/200-240 VAC 50/60 Hz (Auto-ranging)
20.0 - 16.0 Amps and 10.0 - 8.2Amps
(20 Amp max. branch circuit overcurrent protection)
Same as line input power
115 VAC or 230 VAC (+ 10% on battery with full load)
at 50/60 Hz (+ 3 Hz)
100/120-127/200-240 VAC at 50/60 Hz
16.0 - 14.2 Amps and 9.0 - 7.5 Amps Max
< 2.3 Amps (A Peak to A rms)
1.8 kVA max with a 0.5 to 1.0 power factor
True sine wave with < 10% total harmonic distortion
(on a purely resistive load)
AC Failure - < 10 msec to switch to battery power
AC Restored -5 Second delay returning to phase lock to input AC
Phase locked to within 5º of input utility AC
UL, CSA, and TUV
10 Amp/250 VAC
.
Specification
B-21