Description
Electrical Specifications:
AC Line Input:
Rated Voltage
Rated Current
AC Output:
Output VAC
(On Line Power)
Output VAC
(On Battery)
Range VA/Watts
Transfer Time
Phasing
Safety Agency Approvals
Battery:
Type
Nominal open
circuit voltage
Reserve time
Battery Recharge
Time
Optimum Battery
Lifetime
B-16
A2994A PowerTrust UPS Specifications
Table B-22.
100-120/200-240 VAC 50/60 Hz (Auto-ranging)
14 to 12 Amps and 7 to 6 Amps
(20 Amp max branch circuit overcurrent protection)
Approximately equal to AC line input power
115 VAC or 230 VAC at 50/60Hz
(+ 10% with full load)
1300/1300 @ 0.5 to 1.0 power factor
AC Failure - < 10 msec to switch to battery power
AC Restored -5 Second delay returning to input AC phase lock
Phase locked to within 5º of input utility AC
Agency approvals: UL, CSA, and TUV
Maintenance-free, sealed, computer grade, lead-acid type
60 VDC
Approximately 15 minutes (at full load)
< 14 Hours with output switch in the ON position
(after full discharge)
< 24 Hours with output switch in the OFF position
(after full load discharge)
3.5 to 5 years
.
Specification