HP 3000 9X9/KS Site Preparation And Requirements Manual page 64

Enterprise servers
Hide thumbs Also See for 3000 9X9/KS:
Table of Contents

Advertisement

Table B-24.
Description
Battery:
Type
Nominal open
circuit voltage
Battery Runtime
20º C (68º F) or above
New battery
Battery Recharge
Time
Optimum Battery
Lifetime (25º C/77º F) 3.5 to 5 years
Environmental Specifications
Operating
Temperature
Storage Temperature
Operating Altitude
Storage Altitude
Physical Specifications
Electronics Unit
Dimensions
Packaged:
Dimensions
Unpackaged:
B-22
A2997A PowerTrust UPS Specifications
Maintenance-free, sealed, lead-acid type (10 Amp/Hour)
60 VDC
15 minutes over battery lifetime
15 minutes over full temperature range
< 14 Hours (UPS OFF)
< 24 Hours (UPS Operating)
5º to 40º C (41º to 104º F)
15% - 80% relative humidity (non-condensing)
-30º to 50º C (-20º to 122º F) Battery life is shortened severely
when temperature exceeds 25º C (77º F) for extended periods.
5% - 80% relative humidity (non-condensing)
3000 meters (10,000 ft.)
4572 meters (15,000 ft.)
Height - 41.0 cm (16.0 inches)
Width - 57.0 cm (22.5 inches)
Depth - 72.0 cm (28.4 inches)
Weight - 69.0 kg (151.5 lbs)
Height - 25.5 cm (10.0 inches) - 6 EIA rack units
Width - 42.5 cm (16.7 inches)
Depth - 61.0 cm (24.0 inches)
Weight - 63.0 kg (139.0 lbs)
. (Continued)
Specification

Advertisement

Table of Contents
loading

This manual is also suitable for:

9000 k-class

Table of Contents