HP 3000 9X9/KS Site Preparation And Requirements Manual page 67

Enterprise servers
Hide thumbs Also See for 3000 9X9/KS:
Table of Contents

Advertisement

Table B-25.
Description
Battery:
Type
Nominal open
circuit voltage
Battery Runtime
20º C (68º F) or above
New battery
Battery Recharge
Time
Optimum Battery
Lifetime
at < 25º C (< 77º F)
Environmental Specifications
Operating
Temperature
Storage Temperature
Operating Altitude
Storage Altitude
A2998A PowerTrust UPS Specifications
Maintenance-free, sealed, lead-acid type (20 Amp/Hour)
120 VDC
15 minutes over battery lifetime
15 minutes over full temperature range
< 14 Hours (UPS OFF) (at 20º C (68º F) or above)
< 24 Hours (UPS Operating) (at 20º C (68º F) or above)
4 years
5º to 40º C (41º to 104º F)
15% - 80% relative humidity (non-condensing)
-30º to 50º C (-20º to 122º F) Battery life is shortened severely
when temperature exceeds 25º C (77º F) for extended periods.
5% - 80% relative humidity (non-condensing)
3000 meters (10,000 ft.)
4572 meters (15,000 ft.)
. (Continued)