Location Of Ice Machine; Ice Machine Heat Of Rejection - Manitowoc S Installation, Use & Care Manual

S model
Hide thumbs Also See for S:
Table of Contents

Advertisement

Section 2

Location of Ice Machine

The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met,
select another location.
The location must be free of airborne and other
contaminants.
The air temperature must be at least 35°F (1.6°C),
but must not exceed 110°F (43.4°C).
Remote air cooled - The air temperature must be at
least -20°F (-29°C), but must not exceed 120°F
(49°C)
The location must not be near heat-generating
equipment or in direct sunlight and must be protected
from weather.
The location must not obstruct air flow through or
around the ice machine. Refer to the chart below for
clearance requirements.
S300
Top/Sides
Back
S320/S450/S500/
S600/S850/S1000
Top/Sides
Back
S420
Top/Sides
Back
S1200
Top
Sides
Back
S1400/S1600/S1800
Top/Sides
Back
S3300**
Top/Sides
Back
*There is no minimum clearance required for water-cooled or remote ice
machines. This value is recommended for efficient operation and servicing
only.
**S3300 - 24" on all sides is recommended to allow access without moving the
bin/ice machine.
Part Number 000000966 03/09
Self-Contained
Self-Contained
Air-Cooled
Water-Cooled
16" (40.6 cm)
8" (20.3 cm)
5" (12.7 cm)
5" (12.7 cm)
Self-Contained
Water-Cooled and
Air-Cooled
Remote*
8" (20.3 cm)
8" (20.3 cm)
5" (12.7 cm)
5" (12.7 cm)
Self-Contained
Water-Cooled and
Air-Cooled
Remote*
12" (30.5 cm)
8" (20.3 cm)
5" (12.7 cm)
5" (12.7 cm)
Self-Contained
Water-Cooled and
Air-Cooled
Remote*
8" (20.3 cm)
8" (20.3 cm)
12" (30.5 cm)
8" (20.3 cm)
5" (12.7 cm)
5" (12.7 cm)
Self-Contained
Water-Cooled
Air-Cooled
and Remote*
24" (61.0 cm)
8" (20.3 cm)
12" (30.5 cm)
5" (12.7 cm)
Water-Cooled
8" (20.3 cm)
24" (61.0 cm)
The ice machine must be protected if it will be
subjected to temperatures below 32°F (0°C).
Failure
caused
by
temperatures is not covered by the warranty. See
"Removal from Service/Winterization".

Ice Machine Heat of Rejection

Series
Ice Machine
Air Conditioning
S300
S320
S420
S450
S500
S600
S850
S1000
S1200
S1400
S1600
S1800
S3300
B.T.U./Hour
Because the heat of rejection varies during the ice making cycle,
the figure shown is an average.
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when sizing
air conditioning equipment where self-contained air-
cooled ice machines are installed.
This information is also necessary when evaluating the
benefits of using water-cooled or remote condensers to
reduce air conditioning loads. The amount of heat added
to an air conditioned environment by an ice machine
using a water-cooled or remote condenser is negligible.
Knowing the amount of heat rejected is also important
when sizing a cooling tower for a water-cooled
condenser. Use the peak figure for sizing the cooling
tower.
Installation Instructions
! Caution
exposure
to
freezing
Heat of Rejection
Peak
5000
6000
3800
6000
5900
6900
5900
6900
6100
6900
9000
13900
13000
16000
17700
21000
20700
24500
25000
28000
21000
31000
31000
36000
45000
51000
2-9