Location of Ice Machine

The location selected for the ice machine must meet the
following criteria. If any of these criteria are not met, select
another location.
• The location must be free of airborne and other
contaminants.
• This equipment is intended for indoor use only. Do not
install or operate this equipment in outdoor areas.
• The air temperature must be at least 50°F (10°C), but
must not exceed 110°F (43°C).
• The water temperature must be at least 37°F (3°C), but
must not exceed 90°F (32°C).
• The location must not be near heat-generating
equipment or in direct sunlight.
• The location must be capable of supporting the weight of
the ice machine and a full bin of ice.
• The location must allow enough clearance for water,
drain and electrical connections in the rear of the ice
machine.
• The location must not obstruct airflow through or around
the ice machine.

CLEARANCE REQUIREMENTS

Undercounter Units
Top
Sides
Back
NOTE: Allowance must be made for removal when the ice machine is built in. Removal
of the top panel is required for de-scaling & sanitizing.
Modular Units
Cooled
Top/Sides
8" (20 cm)
Back
5" (13 cm)
RCUF Units
Front/Back
Sides/Top
24 inches clearance on top and sides is recommended for serviceability.
Part Number 000017542 Rev 00 8/22

Installation Instructions

Air-Cooled
Water-Cooled
0" (0 cm)
0" (0 cm)
2" (5 cm)
2" (5 cm)
8" (20 cm)
8" (20 cm)
Air-
Water-
QuietQube®
Cooled
Air-Cooled
8" (20 cm)
0" (0 cm)
5" (13 cm)
0" (0 cm)
Remote Condensing Unit
24" (61 cm)
6" (15.2 cm)
Section 2

Installation Requirements

• The ice machine and bin must be level.
• Install the bin drain and ice machine drain separately.
• Ice machine drain must be vented.
• Bin drain termination must have an air gap.
• When local code requires, a backflow preventer must be
installed on the water inlet line.
• The ice machine and bin must be sanitized after
installation.
• Local water conditions may require treatment of the
water to inhibit scale formation, filter sediment, and
remove chlorine odor and taste.
• Routine adjustments and maintenance procedures
outlined in this manual are not covered by the warranty.

Ice Machine Heat of Rejection

Series
Ice Machine
UFF0200 - RFF0320 - RFP0320
UNF0200 - UNP0200
UNF0300 - UFF0350
RNF0320 - RNP0320
RFF0620 - RNF0620 - RNP0620
RNF1100 - RNP1100
RFF1300
RFF2500
Ice machines, like other refrigeration equipment, reject heat
through the condenser. It is helpful to know the amount of
heat rejected by the ice machine when sizing air conditioning
equipment.
This information is also necessary when evaluating the
benefits of using water-cooled or remote condensers to
reduce air conditioning loads. The amount of heat added to
an air conditioned environment by an ice machine using a
water-cooled or remote condensing unit is negligible.
Knowing the amount of heat rejected is also important when
sizing a cooling tower for a water-cooled condenser.
Heat of Rejection Btu/h
2400
2800
5000
3075
5200
7500
7500
17000