Parameter Clear, All Parameter Clear - Mitsubishi Electric FR-A700 Instruction Manual

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Operation panel (FR-DU07)
3.2.8

Parameter clear, all parameter clear

POINT
· Set "1" in Pr. CL parameter clear , ALLC all parameter clear to initialize all parameters. (Parameters are not cleared
when "1" is set in Pr. 77 Parameter write selection.)
· Refer to the parameter list on page 88 and later for parameters to be cleared with this operation.
Operation
1.
Screen at powering on
The monitor display appears.
2.
Press
to choose the PU operation
mode.
3.
Press
to choose the parameter
setting mode.
4.
Turn
until "
appears.
5.
Press
to read the currently set value.
"
"(initial value) appears.
6.
Turn
clockwise to change it to
the setting value of " ".
7.
Press
to set.
and
The inverter is not in the PU operation mode.
1. Press
2. Carry out operation from step 6 again.
44
", "
"
· Turn
to read another parameter.
· Press
to show the setting again.
· Press
twice to show the next parameter.
are displayed alternately ... Why?
.
is lit and the monitor (4 digit LED) displays "0" (Pr. 79 = "0" (initial value)).
Display
PU indication is lit.
Parameter clear All parameter clear
Parameter clear
Flicker ··· Parameter setting complete!!
The parameter
number read
previously appears.
All parameter clear