Mitsubishi Electric FR-A700 Instruction Manual page 111

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter List
Parameter
PID control
automatic
127
switchover
frequency
128
PID action selection
PID proportional
129
band
130
PID integral time
131
PID upper limit
132
PID lower limit
133
PID action set point
134
PID differential time
Output interruption
575
detection time
Output interruption
576
detection level
Output interruption
577
cancel level
106
Incre
Initial
Name
ments
Value
0.01Hz
9999
1
10
0.1%
100%
0.1s
1s
0.1%
9999
0.1%
9999
0.01%
9999
0.01s
9999
0.1s
1s
0.01Hz
0Hz
0.1%
1000% 900 to 1100%
Range
Description
Set the frequency at which the control is
0 to 400Hz
automatically changed to PID control.
9999
Without PID automatic switchover function
10
PID reverse action
11
PID forward action
20
PID reverse action
21
PID forward action
50
PID reverse action
51
PID forward action
60
PID reverse action
61
PID forward action
If the proportional band is narrow (parameter
setting is small), the manipulated variable
varies greatly with a slight change of the
measured value. Hence, as the proportional
0.1 to 1000%
band narrows, the response sensitivity (gain)
improves but the stability deteriorates, e.g.
hunting occurs.
Gain K = 1/proportional band
9999
No proportional control
Time required for only the integral (I) action to
provide the same manipulated variable as that
0.1 to 3600s
for the proportional (P) action. As the integral
time decreases, the set point is reached
earlier but hunting occurs more easily.
9999
No integral control.
Set the upper limit value.
If the feedback value exceeds the setting, the
0 to 100%
FUP signal is output. The maximum input
(20mA/5V/10V) of the measured value
(terminal 4) is equivalent to 100%.
9999
No function
Set the lower limit value.
If the measured value falls below the setting range,
0 to 100%
the FDN signal is output.
The maximum input (20mA/5V/10V) of the
measured value (terminal 4) is equivalent to 100%.
9999
No function
0 to 100% Used to set the set point for PID control.
9999
Terminal 2 input voltage is the set point.
Time required for only the differential (D)
action to provide the same manipulated
0.01 to
variable as that for the proportional (P) action.
10.00s
As the differential time increases, greater
response is made to a deviation change.
9999
No differential control.
If the output frequency after PID operation
remains lower than the Pr. 576 setting for
0 to 3600s
longer than the time set in Pr. 575, the
inverter stops operation.
9999
Without output interruption function
Set the frequency at which the output
0 to 400Hz
interruption processing is performed.
Set the level (Pr. 577 minus 1000%) to
release the PID output interruption function.
Para
Param
meter
eter
copy
clear
: enabled
× : disabled
Deviation value
signal (terminal 1)
Measured value
input (terminal 4)
Set value (terminal
2 or Pr. 133)
Deviation value
signal input
(L
W
, CC-Link
ON
ORKS
communication)
Measured value,
set value input
(L
W
, CC-Link
ON
ORKS
communication)
All
param
eter
clear