Installing the Amplifier Unit
Installation procedure
Hook the Sensor Head connector end of the Amplifier Unit on the
DIN Track and press in at the bottom until the Amplifier Unit locks
into place.
Be sure to mount the Amplifier Unit by hooking the Sensor Head
connector end of the Amplifier Unit on the DIN Track.
Hooking the other end may impair the mounting strength of the DIN
Track attachment.
Removal procedure
Push the Amplifier Unit in direction 1 and pull out the Sensor Head
connector end in direction 2.

4. Basic Knowledge for Operation

Switching Modes
To switch the operating mode, use the SET/RUN Switch.
Switch to the desired mode before operating the Amplifier Unit.
Mode
SET
Select this mode to set the sensing conditions or threshold value by teaching.
RUN
Select this mode to perform actual sensing or to set the following:
Manual adjustment of the threshold value, power adjustment, zero reset, key lock
Key Operations
Use the Control Keys to change the display and set sensing conditions.
The currently selected mode determines the key functions.
Key
UP key
Increases the threshold value.
DOWN key
Decreases the threshold value.
MODE key
The function changes depending on the
setting
• Executes a zero reset
• Teaching with and without a workpiece
About key pressing time
Unless otherwise mentioned in text descriptions, press keys for about one second.
Example: Press the UP key.
This means that you hold down the key for about one second and then release the key.
Reading Displays
The data displayed on the main and sub-displays depends on the currently selected mode. When the power is first turned
ON after shipment, RUN mode data is displayed.
Mode
SET
Displays distance values and function names in order when
the Control Keys are pressed.
RUN*
Displays the current distance value. (default)
* Display details can be changed by the display switch function. Refer to "Function Transition Charts" in "5. Function
Overview."
RUN Mode
"
.
Main Display (Red Display)
Hook on sensor head connector
2
Details
Function
The function changes depending on the settings.
• Executes teaching.
• Changes the setting value in the forward direction.
The function changes depending on the settings.
• Executes teaching.
• Changes the setting value in the reverse direction.
"
Changes the display to the function to be set.
MODE key
Displays the threshold values and setting values of
functions currently displayed on the main display in order
when the Control Keys are pressed.
Displays the current threshold value. (default)
- 4 -
DIN track
1
DIN track
SET Mode
Sub-Display (Green Display)