Status word according to profidriveprofile
The Status word is used to notify a master (e.g.
a PC) about the status of a slave.
Bit
Bit = 0
00
Control not ready
01
VLT not ready
02
Coasting
03
No error
04
ON 2
05
ON 3
06
Start possible
07
No warning
Speed ≠ reference
08
09
Local operation
10
Not in operation range
11
No operation
12
VLT OK
13
Voltage OK
14
Torque OK
15
Timer OK
Bit 00, Control not ready/ready
In the case of bit 00 = "0", bit 00, 01 or 02 of the Control
word is "0" (OFF 1, OFF 2 or OFF 3) - or the frequency
converter has switched off (trip). In the case of bit 00 =
"1", the frequency converter control is ready, but there
is not necessarily a supply to the power unit present (in
the case of external 24 V supply of the control system).
Bit 01, VLT not ready/ready
Same significance as bit 00, however, there is a supply
of the power unit. The frequency converter is ready
when it receives the necessary start signals.
Bit 02, Coasting/Enable
In the case of bit 02 = "0", bit 00, 01 or 02 of the
Control word is "0" (OFF 1, OFF 2 or OFF 3 or coasting)
- or the frequency converter has switched off (trip).
In the case of bit 02 = "1", bit 00, 01 or 02 of the Control
word is "1"; the frequency converter has not tripped.
Bit 03, No error/Trip
In the case of bit 03 = "0", no error condition
of the frequency converter exists.
MG.90.G1.02 - VLT is a registered Danfoss trademark
Bit =1
Ready
Ready
Enable
Trip
OFF 2
OFF 3
Start not possible
Warning
Speed = reference
Bus control
Frequency limit OK
Operation
Stopped, autostart
Limit exceeded
Limit exceeded
Limit exceeded
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA PROFIBUS
In the case of bit 03 = "1", the frequency converter has
tripped and requires a reset signal before it can start.
25