Detailed Explanation Of Setting Modes; Filter Sign Setting - Daikin SkyAir RZQ200 · 250C7Y1B Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

SiBE26-701
1.3

Detailed Explanation of Setting Modes

1.3.1 Filter Sign Setting

If switching the filter sign ON time, set as given in the table below.
Set Time
Mode No.
1.3.2 Ultra-Long-Life Filter Sign Setting
When a Ultra-long-life filter is installed, the filter sign timer setting must be changed.
It blinks based on the "filter cleaning" display interval.
Setting Table
1.3.3 Selection of Thermistor
Select the thermistor to control indoor temperature.
The factory setting for the Second Code No. is "02" and indoor temperature is controlled by the
indoor unit suction air thermistor.
When the Second Code No. is set to "01," the suction air thermistor and the remote controller
thermistor are concurrently operated. Their control is shown in the upper right figure.
1.3.4 "Filter Cleaning" Displayed or Not Displayed
Whether or not to display "Filter Cleaning" after operation of certain duration can be selected.
Field Setting
First
Second
Code No.
Code No.
10 (20)
0
01
02
Mode No.
Setting Switch No.
10 (20)
Mode No.
10 (20)
36
34
When cooling
32
Suction air
Remote controller
30
thermistor
thermistor
Suction air
Remote controller
28
thermistor
thermistor
26
24
22
20
21
23
25
27
29
Air temperature(ºC)
Mode No.
10 (20)
Filter Specs.
Standard
Long Life
200 hrs.
2,500 hrs.
100 hrs.
1,100 hrs.
Setting Position No.
1
First Code No.
Second Code No.
2
32
30
28
26
Suction air
thermistor
24
Suction air
thermistor
22
20
18
16
14
31
33
35
37
14
First Code No.
Second Code No.
3
Field Setting of Indoor Unit
Ultra Long
Life Filter
10,000 hrs.
Contamination
Light
5,000 hrs.
Contamination
Heavy
01
Long-Life Filter
02
Ultra-Long-Life Filter
Thermistor that controls
indoor temperature
Indoor air thermistor for
remote controller and
01
suction air thermistor for
indoor unit
Suction air thermistor for
02
indoor unit
When heating
Suction air
Remote controller
thermistor
thermistor
Suction air
Remote controller
thermistor
thermistor
16
18
20
22
24
26
Air temperature(ºC)
"Filter Cleaning" Display
01
02
Setting
Setting
Suction air
thermistor
Suction air
thermistor
28
30
Yes
No