Troubleshooting
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check connectors for
connection.∗1
Normal?
∗2
YES
Remove thermistor from
outdoor unit PC board,
then measure the
resistance using a tester.
Normal?
∗2
YES
∗1 : H9 : Malfunction of outdoor temperature thermistor system
J3 : Malfunction of discharge pipe thermistor system
J5 : Malfunction of suction pipe thermistor system
J6 : Malfunction of heat exchange thermistor
J9 : Malfunction of thermister circuit at the outlet of subcooloing heat exchanger
See
Check No. 6
for "Thermistor temperature/Resistance characteristics".
∗2 : The number of each thermister and the connector
Name
Outdoor air thermistor
Suction pipe thermistor
Discharge pipe thermistor
Heat exchanger thermistor
Subcooling heat exchanger outlet thermistor
NO
NO
Connector
Symbol
Connector No.
R1T
X18A
R2T
X30A
R3T
X29A
R4T
X30A
R5T
Diagnosis by Remote Controller
Connect correctly.
Replace the thermistor.
When a set of
integrated thermister
is equipped, replace
it as a set.
Replace the outdoor
unit PC board
(A1P).
RZQ
·
200
250C
Pin No.
1-2
3-4
5-6
137