4. Diagnosis by Remote Controller

4.1

Confirm Method of Malfunction Code

4.1.1 Self-diagnosis by Wired Remote Controller
Explanation
If operation stops due to malfunction, the remote controller's operation LED blinks, and
malfunction code is displayed. (Even if stop operation is carried out, malfunction contents are
displayed when the inspection mode is entered.) The malfunction code enables you to tell what
kind of malfunction caused operation to stop. See page 102 for malfunction code and
malfunction contents.
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds
Troubleshooting
Display of indoor unit for
which a malfunction has
been detected
Inspection display
Inspection/Test button
or more will clear the failure history indication shown above. In this case, on the codes
display, the malfunction code will blink twice and then change to "00" (=Normal), the Unit No.
will change to "0", and the operation mode will automatically switch from check mode to
normal mode (displaying the set temperature).

Diagnosis by Remote Controller

Operation LED
ON/OFF button
Malfunction code
99