Daikin SkyAir RZQ200 · 250C7Y1B Service Manual page 47

R-410a heat pump 50hz
Table of Contents

Advertisement

Field Setting of Outdoor Unit
1. Connect the demand adapter X80A to X36A and X66A on the outdoor unit control PCB.
2. According to the desired demand, short-circuit between the terminals on the demand
2.2.2 Low Noise Operation by External Input
External input enables low noise operation by restricting outdoor fan rotation speed and
compressor operation frequency. (Use at night or other time when the load is small.)
1. Turn ON the DIP Switch (DS1-3) on the outdoor unit control PCB.
2. Short-circuit between the terminal blocks X801M and COM on the demand adapter. (Low
3. Low noise level setting can be changed in the field setting with the remote controller, as
4. Furthermore, "Required capacity prior" can be selected in the field setting with the remote
Low noise level
Mode
Mode 1
Mode 2
Mode 3
36
Setting Procedure
adapter terminal block X801M.
[Input signals]
Normally a contact
Input current for each contact is approximately 12 mA.
As an input contact, use a contact for minute electric current.
Use the minimum applicable load (operable at 12 VDC or less,
1 mA or less)
[Field wiring specifications]
Recommended cable : sheathed vinyl cables or double-core cables
0.75 - 1.25 mm
Wiring length
: 100 m or less
In order to prevent a malfunction, separate
from power cables.
Setting procedure
noise operation is performed while being short-circuited.)
needed.
controller, as needed.
Description
Low noise level 1
Low noise level 2
Low noise level 3
Terminal block X801M
Demand 1
Short-circuit between "COM" and "1"
Demand 2
Short-circuit between "COM" and "2"
Demand 3
Short-circuit between "COM" and "3"
2
*Input signals and field wiring
specifications are same as the
specifications above.
SiBE26-701
Setting procedure
Field Setting