Troubleshooting Based on Equipment Condition
2.11 Remote Controller LCD Displays "88"
Applicable Model
All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Cause
Troubleshooting
96
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Trouble
generates just after power
supply ON
NO
Is the
position of (SS 1) on
indoor unit PC board at
"Emergency"?
NO
Check the unit based on
indoor unit LED and outdoor
unit LED. (Trouble Shooting)
YES
YES
SiBE26-701
The unit is checking to confirm
that remote controller is normal.
Indication appears for short time.
Turn the switch to "Normal", and
reset power supply.
(S1999)
Troubleshooting