Field Setting of Indoor Unit
1.3.12 Air Flow Adjustment - Ceiling Height
Make the following setting according to the ceiling height. The setting position No. is set to "01"
at the factory.
13 (23)
* FFQ can not set two ways outlets.
13 (23)
13 (23)

1.3.13 Air Flow Direction Setting

Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting Table
* FFQ can not set two-direction air flow.
1.3.14 Setting of Air Flow Direction Adjustment
Only the model FBQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
Down-flow operation: Yes
Down-flow operation: No
30
In the Case of FHQ, FAQ
Setting Switch
Mode No.
No.
13 (23)
0
In the Case of FUQ, FFQ
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
In the Case of FCQ50~71
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.8 m
In the Case of FCQ100~125
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m
Mode No.
First Code No.
13 (23)
1
Setting
Setting Position
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
Setting
4-way Outlets
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
Setting
4-way Outlets
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.0 m Lower than 3.5 m Lower than 3.8 m
Setting
4-way Outlets
Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
Second Code
No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow*
Mode No.
First Code No.
13 (23)
SiBE26-701
Setting
Ceiling height
3-way Outlets
2-way Outlets*
Ceiling height
3-way Outlets
2-way Outlets
Ceiling height
3-way Outlets
2-way Outlets
Setting
Second Code No.
01
3
02
Field Setting