Boiler Operational Sequence - Thermal Solutions EVS SERIES Installation, Operating And Service Instructions

Evs series modulating boiler
Table of Contents

Advertisement

VI. Boiler Operational Sequence
Product Features
Boiler Sequence
BOILER STATE
LCD Display
Parameter / Notes
Boiler Disable or Remote On/Off
Outdoor Air Temp >
Warm Weather Shutdown Setpoint
Domestic Hot Water Priority
Fuel Valve Energized
Flame Safeguard Alarm
System Pump Feedback
Recycling Limits
( LC, OO, WF , GP and HL inputs )
Non-Recycling Limits
(Combustion Air Flow (CA Input))
Call For Heat Relay
Lockout Indicator
(Manual Reset Required)
System Pump Backup Pump
Combustion Air Damper
Mixing Valve Output
Blower High Speed
Blower 0 Volts
Notes
a.
Boiler Pump is "On" when the Boiler Pump is set to "On Always" or the boiler is lead boiler and Boiler Pump is set to "On Lead".
b.
Boiler Pump is "On" when the Boiler Pump is set to "On Always" and WWSD is set to "WWSD of System Pump" or "Off".
c.
System Pump is "On" when the System Pump is set to "yes" and WWSD is set to either "WWSD of Boiler" or "Off".
d.
Boiler pump is "On" during Prepurge and Post Purge when Boiler Pump is set to "Purge" or boiler is lead & Boiler Pump is set to "On Lead".
e.
Combustion Air Damper Spare Output is maintained "On" for 2 minutes after the Call For Heat is removed.
f.
Modulation rate is held at purge % when low fire input is not provided.
Sage Boiler Control Instruction Manual
a
RO
-
44,30,
O+,O-
75
DP
20,74
Low Fire Hold
SI
9
CS
-
AL
-
SI
9
70,71,
Call For Heat
R+,R-
OR
72
B O, B C
8,27,
LC, OO ,WF,
GP ,HL
28
CA
-
CH
-
LO
-
Spare Output
VI
-
Boiler Pump
BP
2,30
System Pump
SP
25,30
SO
10
10,27/
SO
e
System Alarm
SO
10
6,79,
MS,MR
80
V+,V-,
49
P+,P-
V+,V-,
Purge %
52
P+,P-
V+,V-,
Modulation
-
P+,P-
V+,V-,
Low Fire %
9,51/f
P+,P-
V+,V-,
50
P+,P-
Pre-Sequence States
b &c
a
a
3/d
Boiler Enable/Disable On
Domestic Hot Water Demand Monitored
System Pump Feedback Monitored
Starts in response to System Pump Feedback Input SI
Alarm Status is Monitored
Page 6 of 52
49
Start/Stop Sequence States
-
-
-
-
53
Call For Heat
Recycling Limits Made
Non-Recycling Limits Made
Call For Heat Relay On
Spare Output On
Boiler Pump On
System Pump On
Combustion Air Damper Open
Modulate
-
54/d
4/d