Thermal Solutions EVS SERIES Installation, Operating And Service Instructions page 83

Evs series modulating boiler
Table of Contents

Advertisement

EVCA Modulating Fire Test Procedures and Specifications
APPENDIX D (Cont...) - TSBC
E.
BOILER CONFIGURATION MENU
Factory
Display
Setting
Display
Deg F
Units
Boiler
None
Purge
Pump
Pump
15
Prepurge
Postpurge
5
Delta
Inlet
Yes
Sensor
Mixing
No
Yes
Valve
Set
-
Time/Date
Spare
Off
Input
Yes
Fuel limit
Spare
Off
output
Range/
Description
Choices
Deg F
Selects how temperature parameter values are displayed.
Deg C
None:
None
Always On:
Always On
Purge:
Purge
Lead On
Lead On:
Sets length of time the boiler pump will be run prior to closing the "Call for Heat"
0 to 600 (s)
relay (CH).
Only visible when Boiler Pump does not equal None.
Defines the temperature above BIT that BOT must be at or below before turning off
0 to 20
the boiler pump during pump post purge (Pump Cooldown State).
(C or F)
Only visible when Boiler Pump does not equal None.
No
Enables the inlet temperature display and control logic.
Yes
No
Enables the mixing valve control output and user display.
Yes
hour : minute
Sets the time and date of the boiler's real time clock. This item also displays the
Month / day /
time and date.
year
Sets the function of the Spare Input Terminal (SI).
Off:
Sys Pump Feedback: Input (SI) should be wired to a flow switch inserted in the flow
Off
Sys Pump
FB
Low Fire
Low Fire:
No
Specifies whether high and low gas pressure switches are connected to input (GP).
Yes
Enables Fuel Limit Hold and alarm messages.
Sets the function of the Spare Output Terminal (SO).
Off:
Off
CAD:
CAD
System
System Pump BU:
Pump BU
Soft Alarm
Soft Alarm:
Page 12 of 22
BOILER CONFIG Menu
TM
No Boiler Pump.
Pump Runs Continuously.
Pump Runs during pump pre/post purge operations and during call
for heat and then turns off.
Lead boiler's pump runs continuously when the boiler is the lead
boiler and reverts to "Purge" operation when it is a lag boiler.
Ignore.
path of the primary system pump. Input (SI) indicates the
primary system pump is operating. If output (SO) is set to
System Backup Pump, system pump output (SO) is
energized and System pump Feedback is de-energized the
System Backup Pump output (SO) is energized.
When the Fuel Valve Energized input (CS) is not energized
and Input (SI) is energized the modulation rate is set to the
"Low Fire Spd" setpoint. When input (SI) is not energized
the modulation rate is set to "Fan Purge Spd" setpoint.
When the fuel valve energized input (CS) is energized input
(SI) is ignored.
Never close output (SO).
Closes SO relay with a call for heat, Opens SO relay 2
minutes after call for heat has been de-activated.
Closes when System Pump output is activated but the
System Pump Feedback indicates the Primary System
Pump is not operating.
Closes when a any alarm is active.
83