Thermal Solutions EVS SERIES Installation, Operating And Service Instructions page 6

Evs series modulating boiler
Table of Contents

Advertisement

31.0
[787.4]
EVS-1000
28.3
[717.6]
Boiler Model
Number
INPUT
(MBH)
EVS-1000
1,000
EVS-1500
1,500
BOILER MODEL RANGE
EVS-1000/1500
EVS-1500
10.0
[254.0]
WATER FLOW
SWITCH
P&T GAUGE
30.3
[768.4]
11.8
[298.5]
GROSS
NET AHRI
OUTPUT
RATING
(MBH)
(MBH)
819
1,251
SUPPLY (volts/Hz/phase)
120/60/1
208/60/1
230/60/1
208/60/3
230/60/3
460/60/3
10.0
[254.0]
31.0
[787.4]
WATER FLOW
SWITCH
P&T GAUGE
28.3
30.3
[768.4]
[717.6]
Figure 1b: Dimensions and capacities EVS 1000 & 1500
REQUIREMENT
FOR BURNER
REMOVAL
GAS VENT
3
" NPT PIPE
4
RELIEF
VALVE
WATER SUPPLY
4.4
TO SYSTEM
[111.1]
3" NPT
6.1
[155.6]
CONDENSATE
5
DRAIN
" TUBE
8
BOILER DRAIN
1" NPT PIPE
WATER
VOLUME
(gallons)
2
712
16.4
1,088
17.4
ELECTRICAL
Blower Motor (hp)
1-1/2
REQUIREMENT
FOR BURNER
REMOVAL
GAS VENT
3
" NPT PIPE
4
RELIEF
VALVE
WATER SUPPLY
TO SYSTEM
3" NPT
4.4
[111.1]
6.1
[155.6]
CONDENSATE
11.8
DRAIN
5
" TUBE
8
[298.5]
BOILER DRAIN
1" NPT PIPE
6
6.3
[158.8]
9.3
3.5
[235.0]
[88.9]
GAS PILOT
1
" TUBE
4
WATER RETURN
FROM SYSTEM 3" NPT
19.0
[482.6]
FLUE OUTLET
6" SAF-T-VENT
13.9
[352.4]
9.6
[242.9]
CAPACITIES
DRY WEIGHT
(lbs.)
1,185
1,327
Nominal power draw
6.3
[158.8]
9.3
3.5
[235.0]
[88.9]
GAS PILOT
1
" TUBE
4
WATER RETURN
FROM SYSTEM 3" NPT
19.0
[482.6]
FLUE OUTLET
6" SAF-T-VENT
13.9
[352.4]
9.6
[242.9]
Notes:
1. Piping removed
for visual clarity
(rear view).
2. See notes
concerning Net
AHRI Ratings on
page 4.
WET WEIGHT
(lbs.)
1,322
1,472
(amps)
7.5
6.6
6.4
6.0
6.0
3.0

Hide quick links: