APPENDIX D (Cont...) – TSBC
F.
SYSTEM CONFIGURATION MENU
Factory
Display
Settings
DHWP
Off
Remote
No
Control
Remote
140
1.0 volt =
Remote
220
9.0 volt =
Remote
No
Control
Sensor
System
No
Pump
LWC
Yes
or
(If
CAD
applicable)
"Low
"Low
Water
Water
Level"
Level"
Range
Enables Domestic Hot Water Priority (DHWP) control feature. When input (DP) is
energized DHWP becomes active as selected.
Off:
Off
Isolated Demand: Boiler that receives the input (DP) drops off the Peer-To-Peer
Isolated
Demand
Shared
Demand
Shared Demand: If the lead boiler receives the input (DP) the temperature setpoint for
No
Sets the remote (Energy Management System) control mode as follows.
Remote
No:
SP
Modbus
Remote SP:
SP
Remote
Modbus SP:
Mod
Remote Mod:
Modbus
Modbus Mod:
Mod
Sets the temperature corresponding to input (C+,C-) 1V. Voltage below 1V is
60 F to
considered invalid, (failed or miss wired sensor).
170 F
Only visible when Remote Control equals Remote SP.
Sets the temperature corresponding to input (C+,C-) 9 Volts. Voltage above 9V is
150 F to
considered invalid, (failed or miss wired sensor).
220 F
Only visible when Remote Control equals Remote SP.
Enables the Remote System Temperature sensor display and control logic.
No
No:
Display
Display Only:
Only
Control:
Control
No
Enables the System Pump output (SO).
Yes
No
Specifies a Low Water Cut-off Switch or Combustion Air Damper (Fresh Air Damper).
Yes
Open switch is connected to input (LC). Enables Limit Hold and Alarm Messages.
Only visible if LWC or CAD is selected. The Limit hold and Alarm message displayed
16 Text
corresponding to the sensor connected to input (LC). The "Enter" key and "Up" and
Characters
"Down" arrow keys are used to change the text message.
SYSTEM CONFIG Menu
TM
Description
No DHWP.
network and it's temperature setpoint is adjusted above the DHWP
Setpoint. The PID output is based on boiler outlet temperature and
setpoint. If Remote SP or Remote System temperature sensors were
selected, control is switched to the Boiler Outlet Sensor.
all boilers on the peer-to-peer network is adjusted above the DHWP
Setpoint.
Local setpoint and modulation rate is used. Modbus and remote
input (C+,C-) are ignored.
Remote Input (C+, C-) is used as the temperature setpoint.
Parameter 22 & 23 may be used to adjust the signal range.
RS485 Modbus (40006) is used as the temperature setpoint.
Remote Input (C+, C-) is used as the modulation rate.
RS485 Modbus (40006) is used as the modulation rate.
Remote Sensor Input (R+.R-) is ignored.
Remote Sensor Input (R+,R-) is used for display only.
Remote Sensor Input (R+,R-) is compared with the temperature
setpoint to establish a modulation rate.
Page 13 of 22