TROUBLESHOOTING GUIDE
Alarm Messages
Alarm Messages are shown one at a time in priority order. The message closest to the top of this list is displayed first.
Following messages are not shown until the higher priority message has cleared. All alarm messages are also stored
in the Fault History.
LCD Display
Recommended
Alarm Message
Manually Reset the Low
Low Water Level
Off Switch
Turn Burner Switch On
Ensure Boiler Pump is
Running and Boiler
Low Water Flow
Manually Reset the Fuel
Fuel Limit
Pressure Switch
Manually Reset the
High Temp Limit
High Temperature
Check Combustion Air
Low Air Flow
Pressure Switch
Settings and Wiring
Manually Reset
Required, Refer to
FSG Fault
Flame Safeguard
Corrective Actions
Check Wiring and
Outlet Temp Fail
Check Wiring and
Inlet Temp Fail
Check Wiring and
OA Temp Fail
Check Wiring and
Remote Temp Fail
Action
Low Water Cutoff Switch
When this option is configured and an instrument is installed, the manual reset
low water safety relay is preventing the boiler from starting. If terminal (LC) does
Water Cutoff
not receive power and the Call For Heat output (CH) is powered, the "Low Water
Level" Message is displayed.
Burner Switch is Off
Control switch is in the OFF position and is preventing the boiler from starting. If
terminal (OO) does not receive power and the Call For Heat output (CH) is pow-
ered the "OFF Switch" Message is displayed.
Low Water Flow Switch
Low water flow is preventing the boiler from starting. If terminal (WF) does not
Water Flow is
receive power and the Call For Heat output (CH) is powered, the "Low Water
Unobstructed
Flow" Message is displayed.
Low or High Gas Pressure Switch
The low or high gas pressure switch is preventing the boiler from starting. If
terminal (GP) does not receive power and the Call For Heat output (CH) is
powered the "Fuel Limit" Message is displayed.
High Limit Temperature
The high temperature limit (HL) (and operational temperature limit when
provided) aquastat is preventing a boiler start. If terminal (HL) does not receive
Aquastat
power and the Call For Heat output (CH) is powered, the "High Temp Limit"
Message is displayed.
Low Air Flow or Blocked Vent Switch Not Made
Blower and Air
The air flow (and blocked vent switch when installed) is preventing a boiler start.
If terminal (CA) does not receive power and the Call For Heat output (CH) is
powered, the "Low Air Flow" Message is displayed.
Flame Safeguard Fault
The Flame Safeguard is preventing a boiler start. If terminal (AL) receives power
at any time, the "Flame Failure" Message is displayed.
Manual
Boiler Outlet Temperature Sensor Fail
The boiler outlet temperature sensor is not connected or is reading above or
Sensor
below a valid range. When the boiler outlet sensor fails and the Outlet Sensor
mode was selected, the control will transfer to Lost Sensor Blind Mode.
Boiler Inlet Temperature Sensor Fail
The boiler inlet temperature sensor is not connected or is reading above or below
a valid range. When the boiler inlet sensor fails, the mixing valve output will drive
Sensor
to 0% and low temperature alarm and maximum water differential (boiler outlet
minus boiler inlet) temperature hold are disabled.
Outside Air Temperature Sensor Fail
The outside air sensor is configured and is not connected or is reading above or
Sensor
below a valid range. When the outside air sensor fails, the warm weather shut-
down (WWSD) and outside air reset control logics are disabled.
Remote System Temperature Sensor Fail
The remote system temperature sensor is configured and is not connected or is
Sensor
reading above or below a valid range. If Remote System Temperature Sensor
mode was selected, the control will transfer to Boiler Outlet Sensor Mode.
Explanation
53