Thermal Solutions EVS SERIES Installation, Operating And Service Instructions page 21

Evs series modulating boiler
Table of Contents

Advertisement

TABLE 2 - EVS BOILER FLOW AND PRESSURE DROP
20°DT
(at high fire)
BOILER
MODEL
DP
(Ft.)
EVS-500
2.93
EVS-750
1.81
EVS-1000
3.24
EVS-1500
7.37
EVS-2000
13.27
EVS-2000S
4.27
EVS-2500
4.34
EVS-3000
4.41
40°DT
(at high fire)
Flow
DP
Flow
(GPM)
(Ft.)
(GPM)
43
0.74
22
62
0.46
31
82
0.81
41
125
1.85
63
170
3.32
85
173
1.36
87
217
1.43
109
261
1.73
131
Figure 8: Water Piping (Single Boiler)
Minimum Flow
Maximum Flow
Rate (gpm)
Rate (gpm)
22
31
44
63
85
87
109
131
21
Supply/Return
Pipe
(inch dia.)
43
2
62
3
82
3
125
3
170
3
173
4
217
4
261
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents