OBJECT MAP
Bit map of inverter status monitor/running command is as follows.
Inverter status monitor (Get)
Bit
Signal
0
Running (RUN signal)
1
During forward rotation
2
During reverse rotation
3
Up to frequency (SU signal)
4
Overload alarm (OL signal)
⎯ (Not used)
5
6
Frequency detection (FU signal)
7
Alarm (ALM signal)
8 to 14 ⎯ (Not used)
Inverter operation ready
15
(RY signal)
74
1 : Inverter output frequency reaches or exceeds Pr.13 Starting frequency.
0 : Other than forward rotation (stop, reverse rotation)
1 : During forward rotation
0 : Other than reverse rotation (stop, forward rotation)
1 : During reverse rotation
1 : Output frequency has reached the set frequency
1 : Overload alarm occurrence
(Always 0)
1 : Output frequency reaches or exceeds the frequency set in Pr. 42 (Pr.
43 for reverse rotation).
1 : Output when the inverter protective function is activated to stop the
output (major fault).
(Always 0)
1 : Output reset process is completed (when the inverter can be started
by switching the start signal on or while it is running) after powering
on the inverter.
Description