Class 0X2A (Ac Drive Object); Class 0X2A Instance 1 - Mitsubishi Electric FR-A7ND E kit Instruction Manual

Plug-in option
Hide thumbs Also See for FR-A7ND E kit:
Table of Contents

Advertisement

OBJECT MAP
7.7

Class 0x2A (AC Drive Object)

7.7.1

Class 0x2A Instance 1

(1) Attribute
Class 0x2A Instance 1
Attribute
Access
ID
3
Get
4
Get/Set
6
Get
7
Get
8
Get/Set
70
Name
AtReference
(up to frequency)
NetRef
(operation command
source) (Pr. 339)
DriveMode
(operation mode)
SpeedActual
0 to 32767r/min
(actual speed)
SpeedRef
0 to 32767r/min
(speed setting value)
Range
Output frequency has not reached the set
0
frequency
Output frequency has reached the set
1
frequency
Other than DeviceNet
0
communication
operation (Pr. 339 = "1")
DeviceNet
1
communication
operation (Pr. 339 = "0")
0
Always 0
The output frequency converted to speed is
returned. (1r/min increments)
(Refer to page 42 for conversion formula of speed
and frequency.)
Set speed (1r/min increments)
(Refer to page 42 for conversion formula of speed
and frequency.)
Description
Actual state of
operation command
can be monitored with
Attribute 29.

Advertisement