Class 0x29 Instance 1
Attribute ID Access
9
Get
Ready
10
Get
Faulted
FaultRst
12
Get/Set
(fault reset)
CtrlFromNet
15
Get
(operation command
source monitor)
Instance ID of Input
140
Get/Set
Assembly
Instance ID of Output
141
Get/Set
Assembly
*1
After reset with 01 set, this value must be set to 00 before inverter reset may be performed.
*2
This data is only updated after inverter reset or power-on reset.
*3
When this ID is set, it is reflected to bit7 to 11 of Pr. 346 and Class 0x05 Instance 2 Attribute 7, 13, 14 .
*4
When this ID is set, it is reflected to bit2 to 6 of Pr. 346 and Class 0x05 Instance 2 Attribute 8, 15, 16 .
(2) Service
Service Code
0x0E
Get Attribute Single
0x10
Set Attribute Single
Initial
Name
Value
1
0
0
*1
1
*2
0x47
(71)
*2, *3
0x15
(21)
*2, *4
Description
Range
0
During reset or alarm occurrence
1
Stop or running
0
No fault present
1
Fault occurred (latched)
0
Reset release at fault occurrence
1
Reset execution at fault occurrence
Other than DeviceNet communication
0
operation
1
DeviceNet communication operation
0x46
Input Instance 70
0x47
Input Instance 71
0xB0
Input Instance 176
0x14
Output Instance 20
0x15
Output Instance 21
0x7E
Output Instance 126
OBJECT MAP
Description
7
69