(3) Loosen the terminal screw and insert the cable into the terminal
according to the terminal arrignment.
Tighten each cable with fixing screws to the recommended tightening torque.
Screw Size Tightening Torque
0.5N•m to
M3
0.6N•m
CAUTION
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short
circuit or malfunction due to damage to the screw or unit.
(4) Connect the terminal block to the connector for communication of the communication option mounted
on the inverter.
Cable Size
Screwdriver
Small
flat-blade screwdriver
2
0.3mm
to
(Tip thickness: 0.4mm/tip
2
0.75mm
width: 2.5mm)
WIRING
V- (black)
CAN- (blue)
Shielded cable
CAN+ (white)
V+ (red)
Terminal layout
17