Mitsubishi Electric FR-A7ND E kit Instruction Manual page 82

Plug-in option
Hide thumbs Also See for FR-A7ND E kit:
Table of Contents

Advertisement

Run command (Set)
Bit
Signal
⎯ (Not used)
0
1
Forward rotation command
2
Reverse rotation command
High speed operation command
3
(terminal RH function)
Middle speed operation command
4
(terminal RM function)
Low speed operation command
5
(terminal RL function)
⎯ (Not used)
6
Second function selection
7
(RT signal)
*3
Terminal 4 input selection
8
(AU signal)
*3
⎯ (Not used)
9
Output stop
10
(terminal MRS function)
⎯ (Not used)
11
12
Reset (terminal RES function)
13 to 15 ⎯ (Not used)
(Always 0)
0 : Stop command
*2
1 : Forward rotation start
0 : Stop command
*2
1 : Reverse rotation start
*1
Functions assigned to terminal RH, RM and RL are activated.
*1
*1
(Always 0)
1 : Second function is selected.
1 : Terminal 4 input is the main speed.
(Always 0)
Functions assigned to terminal MRS are activated.
*1
(Always 0)
Functions assigned to terminal RES are activated.
*1
(Always 0)
OBJECT MAP
Description
A starting command is input to the
inverter when the signal turns on.
A stop command is given when both
signals turn on simultaneously.
7
75