INVERTER SETTING
(2) Selection of control source for the network operation mode (Pr. 338, Pr. 339)
⋅ As control sources, there are the operation command source that controls the signals related to the
inverter start command and function selection and the speed command source that controls the
signals related to frequency setting.
⋅ In network operation mode, the commands from the external terminals and communication (PU
connector or communication option) are as listed below.
Pr. 338 Communication operation
Operation
command source
Location
Pr. 339 Communication speed
Selection
command source
Fixed
Running frequency from
function
communication
Terminal 2
(terminal-
equivalent
Terminal 4
function)
Low-speed operation
command/remote setting
0
RL
clear/stop-on contact
selection 0
Middle-speed operation
1
RM
command/remote setting
function
High-speed operation
2
RH
command/remote setting
function
Second function selection/
3
RT
stop-on contact selection 1
4
AU
Terminal 4 input selection
5
JOG Jog operation selection
30
0: NET
0:
1:
2:
NET
External
External
NET
—
NET
—
External
—
—
External
NET
External
NET
External
NET
External
NET
—
Combined
—
1: External
0:
1:
2:
NET
External
External
NET
—
NET
—
External
—
—
External
NET
External
NET
External
NET
External
External
—
Combined
External
Remarks
Pr. 59 = "0"
(multi-speed)
Pr. 59 = "1, 2"
(remote)
Pr. 270 = "1"
(stop-on-contact)
Pr. 270 = "1"
(stop-on-contact)