COMPUTER LINK FUNCTION
3) Station numbers do not have to be sequential and may be skipped, e.g. as shown below:
Computer
(2) Communication specifications
Refer to the following table and set the parameters: (%: Factory setting)
Parameter
Description
Number
Communication
332
speed
Stop bit length/
333
data length
Parity check
334
presence/absence
CR, LF instruction
341
presence/absence
CAUTION
The inverter communication will not error if the Pr. 333 "stop bit length" setting differs from the
actual data value.
Station 3
Station 0
Station number setting example
Instruction
Data Setting
Code
H20: Read
3, 6, 12, 24,
HA0: Write
48, 96
(When HFF=3)
H21: Read
HA1: Write
0, 1
(When HFF=3)
H22: Read
HA2: Write
0, 1, 2
(When HFF=3)
H29: Read
HA9: Write
0, 1
(When HFF=3)
Station 1
Station 21
3: 300bps, 6: 600bps, 12: 1200bps, 24: 2400bps,
%
, 192
48: 4800bps,96: 9600bps, 192: 19200bps
0, 10: Stop bit length = 1 bit
1, 11: Stop bit length = 2 bits
%
, 10, 11
0, 1: Data length = 8 bits
10, 11: Data length = 7 bits
0: No parity check
%
1: Odd parity
2: Even parity
0: Without CR and LF
%
, 2
1: With CR only
2: With CR and LF
25
Station 6
Definition