Technical Specifications - Victron energy Quattro 12/5000/200 User's Manual & Installation Manual

Extremely powerful sine inverter, battery charger and automatic switch
Hide thumbs Also See for Quattro 12/5000/200:
Table of Contents

Advertisement

8. Technical specifications

Quattro
PowerControl / PowerAssist
Integrated Transfer switch
AC inputs (2x)
Maximum feed through current (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25 °C (VA)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Load shedding output
CHARGER
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Multi purpose relay
(5)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
Automotive Directive
1) Can be adjusted to 60 Hz; 120 V 60 Hz on request
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
f. 230VAC on inverter output
g. Input voltage ripple too high
h. Temperature too high
12/5000/200
Yes
Yes
Input voltage range: 187-265 VAC
30
9,5 – 17
Output voltage: 230 VAC ± 2%
5000
(3)
4000
3000
7000
92
25
Maximum load: 10A
14,4
13,8
13,2
200
(4)
Yes
Operating temp.: -20 to +50°C (fan assisted cooling) Humidity (non condensing) : max 95%
Material & Colour: aluminium (blue RAL 5012)
Four M8 bolts (2 plus and 2 minus connctions)
EN55014-1, EN 61000-3-2 / EN 55014-2, EN 61000-3-3
24/5000/120
Yes
Yes
Input frequency: 45 – 55 Hz
30
19 – 33
Frequency
5000
4250
3350
7500
94
30
Switches off when no external AC source available
28,8
27,6
26,4
120
4
ja
Yes
a - g
Screw clamp 13mm² (AWG 6)
30
444 x 328 x 240
EN 60335-1, EN 60335-2-29
2004/104/EC
3) Non linear load, crest factor 3:1
4) At 25 ° C ambient
5) Multipurpose relay which can be set for general
alarm, DC undervoltage or genset start signal function
48/5000/70
Yes
Yes
Power factor: 1
30
38 – 66
50 Hz ± 0,1%
:
5000
4250
3350
7800
95
30
57,6
55,2
52,8
70
Yes
Protection category: IP 21
28

Advertisement

Table of Contents
loading

This manual is also suitable for:

Quattro 24/5000/120Quattro 48/5000/70