Victron energy Quattro 12/5000/200 User's Manual & Installation Manual page 24

Extremely powerful sine inverter, battery charger and automatic switch
Hide thumbs Also See for Quattro 12/5000/200:
Table of Contents

Advertisement

5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (L2, L3). These settings are imposed on the whole system by the leader
L1. If a setting is irrelevant for L2, L3 devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (not relevant for L2, L3)
ds8-ds7
Absorption voltage
off
off
14.1 / 28.2 / 56.4
off
on
14.4 / 28.8 / 57.6
on
off
14.7 / 29.4 / 58.8
on
on
15.0 / 30.0 / 60.0
ds6: absorption time 8 or 4 hours (not relevant for L2, L3)
ds5: adaptive charging characteristic (not relevant for L2, L3)
ds4: dynamic current limiter
ds3: UPS function
ds2: converter voltage
ds1: converter frequency (not relevant for L2, L3)
(the wide input frequency range (45-55Hz) is 'on' by default)
Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to 'off').
DS-8 Charging voltage
DS-7 Charging voltage
on
DS-6 Absorption time
on
DS-5 Adaptive charging
on
DS-4 Dyn. current limit
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 230V
1 Frequency: 50Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (lower button to the right of the
DIP switches). The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the 'other settings' can always be recovered.
Float voltage
Storage voltage
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
off
DS-8
off
DS-7
off
DS-6
on
DS-5
on
off
DS-4
off
DS-3
off
DS-2
on
DS-1
on
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Absorption time: 8
hours
5 Adaptive charging: on
4 Dynamic current limit:
off
3 UPS function: off
2 Voltage: 230V
1 Frequency: 50Hz
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV), Gel MK battery
Gel Victron Deep Discharge, Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate batteries (OPzS)
AGM Victron Deep Discharge
Tubular plate traction batteries in semi-float mode
Tubular plate traction batteries in cyclic mode
on = 8 hours
off = 4 hours
on = active
off = inactive (fixed absorption time)
on = active
off = inactive
on = active
off = inactive
on = 230V / 120V
off = 240V / 115V
on = 50Hz
off = 60Hz
DS-8
on
DS-7
off
DS-6
on
DS-5
on
DS-4
on
DS-3
off
DS-2
off
DS-1
on
Step 2
Example 3:
8, 7 AGM 14,7V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: on
3 UPS function: off
2 Voltage: 240V
1 Frequency: 50Hz
Suitable for
AGM spiral cell
DS-8
on
DS-7
on
DS-6
off
DS-5
off
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step 2
Example 4:
8, 7 Tube-plate 15V
6 Absorption time: 4 hours
5 Fixed absorption time
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 240V
1 Frequency: 60Hz
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Quattro 24/5000/120Quattro 48/5000/70

Table of Contents