Technical Specifications; General; Input - Victron energy PALLAS-TG 12/50 User Manual

Table of Contents

Advertisement

6.

TECHNICAL SPECIFICATIONS

6.1

General

Switch on behaviour
Efficiency 12/50
24/30
24/30 110V
24/50
48/25
Temperature range
EMC
Emission
Immunity
Vibration
Safety
6.2

Input

Input voltage range
Input voltage range 3-Ph
Frequency range
Maximum Input current
model:
12/50
24/30
24/30 110V
24/50
24/50 3-Ph
48/25
Input fuse
model:
12/50, 24/30
24/30 110V, 24/50, 48/25
Cos phi / power factor
26
Charger can switch on under every load
83 % at 230Vac and 15Vdc 50A
85 % at 230Vac and 30Vdc 30A
82 % at 110Vac and 30Vdc 30A
85 % at 230Vac and 30Vdc 50A
85 % at 230Vac and 60Vdc 25A
0 ° C until +40 °C, decreasing output power if temperature
> +40ºC
According Council Directive 89/336 EEG
EN 55014 (1993)
EN 61000-3-2 (1995)
EN 61000-3-3 (1995)
EN 55104 (1995)
IEC 68-2-6 (1982)
EN 60335-2-29 (1991)
185 - 265 Vac,
full output power available
Except 24/30 110V: 93,5-132 Vac, full output power available.
320 - 460 Vac 3-Ph, full output power available
45 - 65 Hz,
full output power available
At 230Vac input voltage :
4A at 15V / 50A
4A at 30V / 30A
8.5A at 30V / 30A (110Vac input voltage)
8A at 30V / 50A
3x 3A at 30V / 50A
8A at 60V / 25A
250Vac / 8A
fast 6,3x32mm, or equivalent
250Vac / 12A
fast 6,3x32mm, or equivalent
1,0
Manual Titan

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Skylla-tg 24/30Skylla-tg 24/50Titan 48/25

Table of Contents