Stove and Vent Clearance
Requirements
Minimum Clearances from the Stove
to Combustibles
See figs. 2-3.
Rear:
3" (76 mm) - measured from Draft Hood
Ceiling:
32 1/4" (819 mm) - measured from stove top
Corner:
3" (76 mm) - measured from stove top
Sides:
3" (76 mm - measured from stove top)
All sides: 1" (25 mm)
All vent components must be installed in accordance
with the manufacturer's instructions and within the
terms of their listing. Refer to the manufacturer's
instructions for approved clearances from the vent pipe
to combustible materials.
Minimum Alcove Dimensions
Maintain clearances to combustibles as noted above.
Width:
32" (81 cm)
Depth:
24" (61 cm)
Height:
61" (155 cm)
Approved Wall Pass-Through
Use only 4" Simpson Dura-Vent Wall Thimble #3143 to
pass the vent pipe through combustible walls. See fig. 2.
13 "
33 cm
4 3/4"
12 cm
Figure 2. Approved Wall Pass-Through, Simpson Dura-
Vent Wall thimble #3134.
3 7/8" to 8"
9.8 cm to 20.3 cm
13 "
33 cm
3"
(76 mm)
Figure 2. Parallel Installation Clearances.
3"
(76 mm)
Figure 3. Vent adaptor centerline at minimum clearance
to corner walls.
Mantel Clearances -
Stove shown with standard legs. With Short Legs, subtract
2 1/4" (51 mm) from the clearances indicated below.
52.25”
55 1/4”
49 1/4”
140 cm
133 cm
125 cm
53 3/4”
50 3/4”
136.5 cm
129 cm
Figure 4. Mantel and Trim specifications -
Stove installed with Top Plate flush with fireplace face.
3"
(51 mm)
To Rear Wall
3"
(76 mm)
9 1/2"
(251 mm)
9 1/2"
(251 mm)
3"
(76 mm)
Max. Mantel
Depth
12.5”
10.25”
8”
5.75”
Min. Mantel
3.5”
47 3/8”
(120 cm)
Depth
Max. Trim
Depth = 1”
28 1/2”
72.3 cm
7