SECTION 10 |
Parameter
High DC Input voltage Alarm
& Fault:
• In normal 3 Stage
Charging Mode
• In 4 Stage Equalization Mode
High DC Input Recovery
No Load Power Consumption in
Normal Mode
PoWeR SAVe MoDe
Method of load sensing
value of load to activate and
de-activate Power Save Mode
No Load power consumption in
Power Save Mode
battery Charger Section
Parameter
Nominal Input voltage
Programmable Input voltage Range
Nominal Input Frequency
Input Frequency Range
Input Power Factor
Input Current Crest Factor
Maximum rated AC Input Current
Max AC Input Current at Short Circuit
Bulk Charging Current
Boost (Absorption) voltage
Boost (Absorption) Time
Float voltage
Equalization voltage
68 | SAMLEX AMERICA INC.
Specifications
G4-2012A
(v-Boost +0.8v) ± 0.3v
(v Equalization + 0.6v) ± 0.3v
v-Boost ± 0.3v
35W
Outputs 2 to 3 cycles of 40 vAC load sensing pulses every 2.8 sec
Load < 10W — Activate Power Save Mode; Load > 60W — Return to Normal Mode
g4-2012a
Utility Mode: 57 to 65 Hz for 60 Hz; 47 to 55 Hz for 50 Hz
20A @ 120 vAC
28A @ 85 vAC
80A
•
Maximum: 80A ± 5A
•
Programmable range:
•
10A to 80A (Steps of 10A)
•
Default: 10A
•
Programmable range:
14 to 16 vDC
•
Default: 14.4 vDC
Automatic — based on the amount of time the battery remains in the Bulk Stage:
Programmable range:
13 to 15 vDC
•
Default: 13.8 vDC
Programmable range:
14 to 16 vDC
•
Default: 15.3 vDC
G4-2524A
(v-Boost +1.6v) ± 0.6v
(v-Equalization + 1.2v) ± 0.6v
v-Boost ± 0.6v
45W
5 W
g4-2524a
120 vAC
80 vAC to 140 vAC ± 4%
50Hz / 60Hz (Auto detection); Default: 60 Hz
Generator Mode: 45 to 65 Hz
> 0.8
< 3.0
25A @ 120 vAC
35A @ 85 vAC
90A
•
Maximum: 70A ± 5 A
•
Programmable range: 10A
to 70A (Steps of 10A)
•
Default: 10A
•
Programmable range:
28 to 32 vDC
•
Default: 28.8 vDC
Minimum — 1 hour
Maximum — 12 hours
Programmable range:
26 to 30 vDC
•
Default: 27.6 vDC
Programmable range:
28 to 32 vDC
•
Default: 30.6 vDC
G4-3524A
(v-Boost +1.6v) ± 0.6v
(v-Equalization + 1.2v) ± 0.6v
v-Boost ± 0.6v
45W
g4-3524a
34A @ 120 vAC
48A @ 85 vAC
120A
•
Maximum: 70A ± 5 A
•
Programmable range: 10A
to 70A (Steps of 10A)
•
Default: 10A
•
Programmable range:
28 to 32 vDC
•
Default: 28.8 vDC
Programmable range:
26 to 30 vDC
•
Default: 27.6 vDC
Programmable range:
28 to 32 vDC
•
Default: 30.6 vDC