SECTION 9 |
SYMPToM
Bad Battery:
i)
DC input voltage < 5v for G4-2012A or
< 10v for G4-2524A/G43524A
ii) External DC input fuse blown due to over-
load / reverse polarity (AC input is available)
CAUTIon! Reverse polarity is likely to cause
permanent damage and is not covered by
warranty.
Wiring Error
Protections And Fault Diagnostics Provided by The LCD Alphanumeric Display
Details of diagnostic alphanumeric messages displayed on the LCD related to critical shut down due to fault conditions are given in Table 9.3 below. More
details on the thresholds for activation of these shut down conditions and associated LED / buzzer activations are given in Table 9.2 on page 57 to 59. When
the unit shuts down, it will be required to be reset manually. To reset, switch OFF the unit, remove the cause of the defect and switch ON again.
In some cases, the unit may get latched and will not switch OFF. In such cases, remove the DC & AC input connections, wait for 5 minutes, reconnect
and then switch ON.
TAbLe 9.3: PRoTeCTIonS AnD ASSoCIATeD LCD DISPLAY MeSSAGeS
Short circuit on AC output side in Utility / Generator Mode AC input gets disconnected due to tripping of Circuit Breaker marked "Charger" (40A
Short circuit in Charger Section in Utility / Generator
Mode
Short circuit on AC output side in Inverter Mode
Protections, Operational
Monitoring & fault diagnosis
TAbLe 9.2: PRoTeCTIonS
"Status" LeD -
"Fault"
GReen
LeD - ReD
OFF
ON
OFF
ON
for G4-2012 and G4-2524 and 60A for G4-3524). Pass-through load will be transferred
to the Inverter Section. Inverter Section will shut down due to electronic short circuit
protection.
LCD displays: " Fault Mode, Short Circuit"
The unit will shut down due to electronic short circuit protection if short circuit lasts for
> 10 sec:
Transfer Relay will be de-energized:
Charging will be stopped
AC by-pass output will be shut down
LCD displays: Fault Mode, Short Circuit"
Inverter will shut down due to electronic short circuit protection if short circuit condition
lasts for > 10 sec.
LCD displays: " Fault Mode, Short Circuit"
buzzer Alarm
Constantly ON
LCD displays "Bad Battery"
Disconnect AC input power
Disconnect DC input connection
Recharge battery using external
charger/replace battery / fuse
Reconnect battery and AC input
power
Constantly ON
LCD displays "Wiring Error"
AC input wiring from Utility /
Generator wrongly connected to
AC output terminals
Connect wiring correctly
SAMLEX AMERICA INC. | 59
Remarks