Resetting Hospitality Mode Setpoints to Defaults

Hospitality Setpoint Principles
In Hospitality mode, users have continuing control over single, occu-
pied, and unoccupied setpoints:
• Under the Single Setpoint option, the setpoint will remain at what-
ever value was last selected by a user until a user adjusts the setpoint
again.
• Under the Schedule option, the setpoint values persist even after
switching between scheduled occupied and unoccupied periods.
For example, if a user changes the occupied cooling setpoint to 76°,
the occupied cooling setpoint will remain at 76° on subsequent days
until a user adjusts it again.
To automatically reset setpoints to default values at particular times (e.g,
daily near midnight):
• A building automation system can overwrite the setpoint value ob-
jects. See
Custom Web Graphics on page 17
program section below to determine values to control.
• Custom programming can be put into the FlexStat. See the Control
Basic program section below and
Control Basic Programs
For the Schedule option, add an equivalent of the following Control
Basic lines:
REM Reset Hospitality Mode Setpoints to Schedule
Defaults
IF+
TIME
> 23:59:00
REM 23:59:00 = 11:59 PM
END
RESET_SETPOINTS :
AV4@8 = 78 :
REM UNOCC COOLING SETPT
FlexStat (General)
as well as the Control Basic
Custom Programming on page
THEN GOSUB
RESET_SETPOINTS
AV4.RELINQUISH_DEFAULT = AV4
AV5@8 = 66 :
REM UNOCC HEATING SETPT
AV5.RELINQUISH_DEFAULT = AV5
AV20@8 = 74 :
REM OCC COOLING SETPT
AV20.RELINQUISH_DEFAULT = AV20
AV21@8 = 70 :
REM OCC HEATING SETPT
AV21.RELINQUISH_DEFAULT = AV21
RETURN
For the Single Setpoint option, use this instead:
REM Reset Hospitality Mode Setpoint to Schedule De-
fault
IF+
TIME
> 23:59:00
REM 23:59:00 = 11:59 PM
REM AV27 = UI Setpoint; BV7 = Heat/Cool Mode
END
RESET_SETPOINT :
8.
IF
BV7
THEN
REM COOLING MODE
AV27@8 = 74
ELSE
REM HEATING MODE
AV27@8 = 70
ENDIF
AV27.RELINQUISH_DEFAULT = AV27
RETURN
20
THEN GOSUB
RESET_SETPOINT
Application Guide, Rev L