Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Option
Terminal
Function Name
Code
Symbol
28
DWN
Remote Control Down
Function (motorized
speed pot.)
29
UDC
Remote Control Data
Clearing
31
OPE
Operator Control
32
SF1
Multi-speed Select,
Bit operation Bit 1
33
SF2
Multi-speed Select,
Bit operation Bit 2
34
SF3
Multi-speed Select,
Bit operation Bit 3
35
SF4
Multi-speed Select,
Bit operation Bit 4
36
SF5
Multi-speed Select,
Bit operation Bit 5
37
SF6
Multi-speed Select,
Bit operation Bit 6
38
SF7
Multi-speed Select,
Bit operation Bit 7
39
OLR
Overload Restriction
Source Changeover
40
TL
Torque Limit Selection
41
TRQ1
Torque limit switch 1
42
TRQ2
Torque limit switch 2
Option
Terminal
Function Name
Code
Symbol
44
BOK
Brake confirmation
46
LAC
LAD cancellation
47
PCLR
Pulse counter clear
50
ADD
ADD frequency enable
51
F-TM
Force Terminal Mode
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Input Function Summary Table
ON
Decelerates (decreases output frequency) motor
from current frequency
OFF
Output to motor operates normally
ON
Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
C101 must be set=00 to enable this function to work
OFF
UP/DWN frequency memory is not changed
ON
Forces the source of the output frequency setting
A001 and the source of the Run command A002 to
be from the digital operator
Source of output frequency set by A001 and source
OFF
of Run command set by A002 is used
ON
Bit encoded speed select, Bit 1, logical 1
OFF
Bit encoded speed select, Bit 1, logical 0
ON
Bit encoded speed select, Bit 2, logical 1
OFF
Bit encoded speed select, Bit 2, logical 0
ON
Bit encoded speed select, Bit 3, logical 1
OFF
Bit encoded speed select, Bit 3, logical 0
ON
Bit encoded speed select, Bit 4, logical 1
OFF
Bit encoded speed select, Bit 4, logical 0
ON
Bit encoded speed select, Bit 5, logical 1
OFF
Bit encoded speed select, Bit 5, logical 0
ON
Bit encoded speed select, Bit 6, logical 1
OFF
Bit encoded speed select, Bit 6, logical 0
ON
Bit encoded speed select, Bit 7, logical 1
OFF
Bit encoded speed select, Bit 7, logical 0
ON
Perform overload restriction
OFF
Normal operation
Setting of b040 is enabled
ON
OFF
Max. torque is limited with 200%
ON
Torque limit related parameters of Powering/regen,
and FW/RV modes are selected by the combinations
OFF
of these inputs.
ON
OFF
Input Function Summary Table
ON
Brake wait time (b124) is valid
OFF
Brake wait time (b124) is not valid
ON
Set ramp times are ignored. Inverter output
immediately follows the freq. command.
OFF
Accel. and/or decel. is according to the
set ramp time
ON
Clear the position deviation data
OFF
Maintain the position deviation data
Adds the A145 (add frequency) value
ON
to the output frequency
Does not add the A145 value to the
OFF
output frequency
ON
Force inverter to use input terminals for output
frequency and Run command sources
Source of output frequency set by A001 and source
OFF
of Run command set by A002 is used
73