Hitachi WJ200 Series Quick Reference Manual page 71

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
C102
Reset selection
C103
Restart mode after reset
C104
UP/DWN clear mode
C105
EO gain adjustment
C106
AM gain adjustment
C109
AM bias adjustment
C111
Overload warning level 2
C130
Output [11] on delay
C131
Output [11] off delay
C132
Output [12] on delay
C133
Output [12] off delay
C140
Relay output on delay
C141
Relay output off delay
C142
Logic output 1 operand A
C143
Logic output 1 operand B
C144
Logic output 1 operator
C145
Logic output 2 operand A
C146
Logic output 2 operand B
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"C" Function
Description
Determines response to Reset
input [RS].
Four option codes:
00...Cancel trip state at input signal
ON transition, stops inverter if
in Run Mode
01...Cancel trip state at signal OFF
transition, stops inverter if in
Run Mode
02...Cancel trip state at input ON
transition, no effect if in Run
Mode
03...Clear the memories only
related to trip status
Determines the restart mode after
reset is given, three option codes:
00...Start with 0 Hz
01...Start with freq. matching
02...Start with active freq. matching
Freq. set value when UDC signal is
given to the input terminal, two
option codes:
00...0 Hz
01...Original setting (in the
EEPROM memory at power
on)
Set range is 50 to 200%
Set range is 50 to 200%
Set range is 0 to 100%
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
Applies a logic function to calculate
[LOG] output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
70
Run
Defaults
Mode
Lnitial data
Units
Edit
00
00
-
00
-
100.
%
100.
%
0.
%
Rated current
A
x 1.15
0.0
Sec.
0.0
Sec.
0.0
Sec.
0.0
Sec.
0.0
Sec.
0.0
Sec.
00
00
00
00
00