Hitachi WJ200 Series Quick Reference Manual page 54

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
a058
DC braking time at start
a059
Carrier frequency during DC
braking
A061
Frequency upper limit
A261
Frequency upper limit,
2nd motor
A062
Frequency lower limit
A262
Frequency lower limit,
2nd motor
A063
Jump freq. (center) 1 to 3
A065
A067
A064
Jump freq. width (hysteresis) 1
to 3
A066
A068
A069
Acceleration hold frequency
A070
Acceleration hold time
A071
PID enable
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"A" Function
Description
Sets the duration for DC braking,
range
is
from
seconds
Carrier frequency of DC braking
performance, range is from 2.0 to
15.0kHz
Sets a limit on output frequency
less than the maximum
frequency (A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
less than the maximum
frequency (A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082)
to frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
Up to 3 output frequencies can
be defined for the output to jump
past to avoid motor resonances
(center frequency)
Range is 0.0 to 400.0 Hz
Defines the distance from the
center frequency at which the
jump around occurs
Range is 0.0 to 10.0 Hz
Sets the frequency to hold
acceleration, range is 0.0 to
400.0Hz
Sets the duration of acceleration
hold, range is 0.0 to 60.0
seconds
Enables PID function,
three option codes:
00...PID Disable
01...PID Enable
02...PID Enable with reverse
output
53
Run
Mode
Lnitial data
Edit
0.0
to
60.0
Defaults
Units
0.0
sec.
5.0
sec.
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.0
Hz
0.0
0.0
0.5
Hz
0.5
0.5
0.00
Hz
0.0
sec.